18
DHW PAW-VP - Installation manual – 2020-05
Safety Instructions
2.
The minimum indoor floor space compared with the amount of refrigerant is roughly
as follows: (When the ceiling is 2.7 m high)
0
10 20 30 40 50 60 70 80 90 100 kg
m²
m³
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
229.5
216.0
202.5
189.0
175.5
162.0
148.5
135.0
121.5
108.0
94.5
81.0
67.5
54.0
40.5
27.0
13.5
0.0
Total amount of refrigerant
Min. indoor floor area
(when the ceiling is 2.7 m high)
Min. indoor volume
Range below the
density limit of
0.44 kg/m³
(Countermeasures
not needed)
Range above the
density limit of
0.44 kg/m³
(Countermeasures
needed)