No. SX-DSV03015 - 53 -
Motor Business Unit, Panasonic Corporation
9-4 List of peripheral devices applicable to servo driver
Servo driver
Voltage
spec
Power capacity
(Rated current)
Electromagnetic
contactor
(Rated current/
Released heat
current)
Circuit breaker
(Rated current)
Noise filter
Surge absorber
Noise filter for signals
Power
cable
Motor
cable
MADL*01**
Single
phase
100 V
Approx.
0.4 kVA
20 A
10 A
DV0P4170
(for single
phase)
/
DV0PM20042
/
RTHN-5010
DV0P4190
(for single phase)
/
DV0P1450
(
for 3 phase
)
DV0P
1460
DV0P
1460
DV0P
1460
MADL*11**
MADL*05**
Single/
3 phase
200 V
Approx.
0.5 kVA
MADL*15**
MBDL*21**
Single
phase
100 V
Approx.
0.5 kVA
MBDL*25**
Single/
3 phase
200 V
Approx.
0.9 kVA
MCDL*31**
Single
phase
100 V
Approx.
0.9 kVA
15 A
DV0PM20042
/
RTHN-5010
MCDL*35**
Single/
3 phase
200 V
Approx.
1.3 kVA
MDDL*45**
Single/
3 phase
200 V
Approx.
1.8 kVA
30 A
20 A
DV0P4220
/
RTHN-5030
MDDL*55**
Approx.
2.3 kVA
MEDL*83**
3phase
200 V
Approx.
3.8 kVA
60 A
30 A
DV0PM20043
/
RTHN-5050
DV0P1450
RJ8035
MEDL*93**
MFDL*A3**
Approx.
4.5 kVA
100 A
50 A
DV0P3410
/
RTHN-5050
MFDL*B3**
Approx.
7.5 kVA
Select the specification common to single/ 3 phase 200 V according to the power supply.
To become compliant with European EC directive, make sure to connect a circuit breaker compliant with
IEC standard and UL certification (marked with LISTED) between the power supply and the noise filter.
- Please!
Select a circuit breaker and a noise filter with the capacity comparable to the power capacity
(by taking into account the load condition).
Terminal block and earth terminal
For wiring, use the copper conductor cable of the temperature rating 75deg. Celsius or more.
For the protection earth terminal, use M4 for Sizes A-E, M5 for Sizes F.
The terminal block can be damaged if the screw tightening torque exceeds the maximum value.