Operation monitor LEDs
■
Operation mode selector setting
Selector
number
1 and 2
3
4
Function
Description
Selector position
Terminal station setting
Output operation condition
during a communication error
I/O points setting
Not terminal station
Terminal station
Stop
ON state (maintain its output condition)
64 points
32 input points:
32 output points:
32 points
16 input points:
16 output points:
X110 to X12F
Y110 to Y12F
X110 to X11F
Y110 to Y11F
1 2 3 4
OFF
ON
OFF
ON
OFF
ON
OFF
ON
LED
Description
POWER
COM.
ALARM
ON:
OFF:
Flashing:
ON:
Flashing
slowly:
OFF:
Flashing:
ON:
OFF:
Power is supplied.
Power is not supplied.
Normal communication status (Flashes in approx. 0.2 s intervals)
Not communicating
A communication error occurred at the slave station. The normal slave station
continues I/O control operation. (Flashes in approx. 1 s intervals)
Abnormal condition
Station number setting error
FP-M I/O link board (MEWNET-F) error
Normal
168
7-7. FP-M I/O Link Board (MEWNET-F)
Содержание FP-M Hardware
Страница 1: ...FP M Hardware ACG M0045 1 94 12 FP M Hardware PROGRAMMABLE CONTROLLER ...
Страница 44: ...36 ...
Страница 118: ...110 ...
Страница 266: ...258 RECORD OF CHANGES ACG No Date Description of Changes ACG M0045 1 DEC 1994 First edition RECORD OF CHANGES ...
Страница 267: ......
Страница 268: ......