Probably a self-diagnostic error.
Check the program using the
programming tool.
• Using NPST-GR Software Ver. 3.1
<If you are using MENU 1 screen type>
Open [NPST MENU] by pressing
Esc
, and then select “MONITOR”
to skip to the [MONITOR] subwindow.
In the [MONITOR] subwindow,
select “7. STATUS DISPLAY”.
At the bottom of the [STATUS
DISPLAY] window, you can find
the error code in “( )”, represented
in decimal, and comments in “[ ]”,
as shown on the right.
• Using FP Programmer II
Press the keys on the FP Programmer II
as shown on the right.
When self-diagnostic error occurs, the
screen shown on the right is displayed.
<If you are using MENU 2 screen type>
Open [ONLINE MONITOR
FUNCTION MENU] by pressing
Ctrl
and
F10
together, and then select
“P. STATUS DISPLAY”.
1
(–)
OP
ACLR
1
OP-110
FUNCTION ERR E45
SLF DIAGN ERR CD (50) [BATTERY ERROR]
Error code
Comments
0
ENT
READ
▼
Error code
From page 115
Cancel error status and start operation
again.
• You can cancel the error status in the following ways:
- Turn the power OFF and then ON.
- Cancel the error status using the NPST-GR Software Ver. 3.1 or the FP
Programmer II.
To perform this function, use “OP 112” of the FP Programmer II or [STATUS
DISPLAY] of NPST-GR Software Ver. 3.1. (This function is not available with a
conventional FP Programmer or with NPST-GR Software Ver. 3.0 or earlier.)
- Cancel the error status using the
F148 (ERR)
instruction.
Check the FP-M referring to
page 124, 2. Table of Self-diagnostic
Error Codes.