Operation monitor LEDs
■
Operation mode selector setting
Selector
number
1
2
3
4
5
6, 7,
and 8
Function
Description
Selector position
System configuration
selection
Output operation
condition during a
communication error
Terminal station setting
Error flag (R9036)
setting
Not used
I/O allocation setting
(use I/O address for
expansion board)
I/O link system:
(FP-M – FP-M)
(FP-M – FP3/FP10S)
I/O link system:
[FP-M (master) – FP I/O
transmitter unit (slave)]
Stop
Start (continues I/O control
operation)
Not a terminal station
Terminal station
ON when an I/O link error
occurs
Not setting
————————————
32 inputs:
32 outputs:
48 inputs:
32 outputs:
24 inputs:
16 outputs:
48 inputs:
32 outputs:
24 inputs:
16 outputs:
X110 to X12F
Y110 to Y12F
X70 to X87,
X90 to X107
Y70 to Y7F,
Y90 to Y9F
X70 to X87
Y70 to Y7F
X30 to X47,
X50 to X67
Y30 to Y3F,
Y50 to Y5F
X30 to X47
Y30 to Y3F
1 2 3 4 5 6 7 8
ON
OFF
ON
OFF
ON
OFF
ON
OFF
—
OFF
ON
ON
ON
ON
—
ON
ON
OFF
OFF
—
ON
OFF
ON
OFF
LED
Description
POWER
COM.
ALARM
ON:
OFF:
Flashing:
ON:
Flashing
slowly:
OFF:
Flashing:
ON:
OFF:
Power is supplied.
Power is not supplied.
Normal communication status (Flashes in approx. 0.2 s intervals)
Not communicating
A communication error occurred at the slave station. The normal slave station
continues I/O control operation. (Flashes in approx. 1 s intervals)
Abnormal condition
Station number setting error
FP-M transmitter master board (MEWNET-TR) error
Normal
164
7-6. FP-M Transmitter Master Board (MEWNET-TR)