Operating Instructions Fire alarm system EBL512 G3, V1.1.x
91
25.1
Disable zone (H2/B1)
When a whole zone is disabled, all alarm points within the zone are
disabled except the addressable manual call points. (This function can
depend on convention / country.)
Disabled zones are listed in menu H4/U1 from which it is also
possible to get a print-out.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H2.
H2 Disable or re-enable
"
↵
"
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
"
↵
"
Disable zone:
0
00
(press
↵)
Write the zone number
(e.g. 001)
Disable zone:
0
01
(press
↵)
Press "
↲
" to disable.
"
↵
"
Re-enable time:
H
H:MM
No
Yes
(Default is current time + 3 hours)
Press "
↲
" to disable
without automatic re-
enablement.
or
Accept the time (+ 3
hours) or set another
time (max + 24 hours),
select "Yes" and press
"
↲
" to disable with
automatic re-
enablement.
"
↵
"
Disable zone:
0
00
(press
↵)
LED
Fault /
Disablements
"General
disablements" (L10) will
light up.
Disable another zone or
press "
ESC
". Scroll to
another menu or press
"
ESC
".