Operating Instructions Fire alarm system EBL512 G3, V1.1.x
98
25.7
Disable / re-enable output type (H2/B7)
All outputs
46
programmed as type control (general), fire ventilation
and extinguishing system
47
can for the type respectively be disabled
all at the same time
or
all outputs of these types can be disabled all at
the same time.
All outputs programmed as type interlocking can be disabled all at the
same time.
Disabled control output
means that even if the control expression
(trigger condition) for the output respectively is fulfilled (true), the
output will not be activated.
The outputs in one or more control units can be disabled or the outputs
in all control units.
Disabled control outputs are indicated by LED
Fault / Disablements
"General disablements" (L10) and shown in menu H4/U1 from which
it is possible to get a print-out.
When all outputs have been re-enabled, The LED
Fault / Disablements
"General disablements" (L10) will be turned OFF, if there are no other
disablements in the system.
The outputs will be disabled until re-enabled again (
via this menu).
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H2.
H2 Disable or re-enable
"
↵
"
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
Scroll to menu B7.
B7 Disable/re-enable output type
46
Including Addressable siren 3377 and Addressable sounder base 3379.
47
Also the "Extinguish equipment output" on the German FBP interface
board 4583.