Operating Instructions Fire alarm system EBL512 G3, V1.1.x
25
7.1
Access level 1
With the door closed
7
,
anybody
has access to the push button "Alarms
queued" (P8) to scroll / browse through the queued alarms.
7.2
Access level 2A
After the door has been opened ("Door open" symbol
in the
symbol field),
the user / fire brigade personnel
have access to the
push buttons / keypad to do the following:
Push
button
Operation/function
P1
Silence the buzzer in the c.i.e.
P2
Silence all alarm devices (sounders).
P3
Reset fire alarms. (see below)
NOTE!
Fire alarms
are:
Fire alarm (incl. heavy smoke/heat alarm)
Alert Annunciation (AA) alarm
Key cabinet alarm
Co-incidence alarm (if not reset automatically)
Acknowledged alarm (New Zealand only)
Isolated alarm (New Zealand only)