Operating Instructions Fire alarm system EBL512 G3, V1.1.x
126
29
FAULT Acknowledge (H6)
Regarding fault indication, etc., see chapter "Fault", page 52.
See also chapter "Fault acknowledge", page 69.
All faults and the status / action are stored in the event log and can be
listed, see chapter "Event log (H4/U6)", page 112.
In menu H6 can be listed up to 300 faults:
not corrected / serviced and not acknowledged faults (no status)
not corrected / serviced but acknowledged faults
(acknowledged)
corrected / serviced but not acknowledged faults
(serviced)
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H6.
H6 Acknowledge FAULTS
"
↵
"
Some examples of fault messages:
FAULT: Low battery capacity, control unit 00
yyyy-mm-dd hh:mm
FAULT: No reply zone: 045 address: 06
technical number 000005
yyyy-mm-dd hh:mm serviced
FAULT: No reply zone: 021 address: 05
technical number 000114
yyyy-mm-dd hh:mm acknowledged
Fault 1/3 is selected
This is a list in which
you can scroll. The most
recent fault is on top of
the list. A corrected fault
is indicated by
serviced
.
An acknowledged fault is
indicated by
acknow-
ledged
.
To acknowledge a fault,
select it and press
"
↵
".
The selected fault has
a boarder around it.
"
↵
"
"
↵
"
FAULT: Low battery capacity, control unit 00
yyyy-mm-dd hh:mm acknowledged
FAULT: No reply zone: 021 address: 05
technical number 000114
yyyy-mm-dd hh:mm acknowledged
Fault 1/2 is selected
A corrected / serviced
fault that you acknow-
ledge will disappear from
this list.
59
"ESC"
H6 Acknowledge FAULTS
Scroll to another menu or
press "ESC".
59
When the list is empty, i.e. when all faults are acknowledged and
corrected, you will automatically return to menu H6: