105
15.2.6 Odor
Cut
Control
To reduce the odor released from the unit.
o
Start
Condition
AUTO FAN Speed is selected during COOL or DRY operation.
During freeze prevention control and timer preliminary operation, this control is not applicable.
o
Control
content
Depends on compressor conditions:
Compressor
OFF
→
Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.
Compressor
ON
→
Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.
15.3 Protection Control for Heating Operation
15.3.1 Intake Air Temperature Control
Compressor will operate at limited freq., if indoor intake air temperature is 30°C or above.
15.3.2 Outdoor Air Temperature Control
The Max current value is regulated when the outdoor air temperature rise above 4°C in order to avoid
compressor overloading.
The compressor will be stopped to avoid compressor overloading.
Current Regulated
Free Within Max Limit
2
°
C
Outdoor air temperature
4
°
C
-15°C
-17°C
COMP. ON
COMP. OFF
Outdoor
Air
Temperature