14.4.16 F90 (Power Factor Correction Protection)
Malfunction Decision Conditions
•
During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at
the outdoor unit main PCB senses abnormal high DC voltage level.
Malfunction Caused
•
DC voltage peak due to power supply surge.
•
DC voltage peak due to compressor windings not uniform.
•
Faulty outdoor PCB.
Troubleshooting
YES
When abnormality indication starts again
Supply voltage as specified?
YES
(~28Vdc)
Correct the power supply
Is the DC voltage between P (+) and N (-) terminal normal
between 285~315Vdc)?
Check the supply voltage
Operate the system. Verify PFC abnormality by measuring DC
voltage between P (+) and N (-) terminal at the outdoor unit PCB.
Are the compressor’s winding resistance (U-V, V-W, W-U)
Check the compressor winding resistance:
•
Turn off the power supply and disconnect the harness U, V
and W.
•
Measure
the
winding resistance between U-V,V-W and W-U
•
Replace the compressor
NO
•
Defect in PFC circuitry
•
Replace the outdoor unit PCB
NO
NO
YES
•
Replace the outdoor unit PCB.
For safety reason and to prevent
component breakdown, always
switch off the power before remove
and connect the component.
Содержание CS-PS9JKT
Страница 7: ...7 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Страница 8: ...8 4 Dimensions 4 1 Indoor Unit...
Страница 10: ...10 5 Refrigeration Cycle Diagram...
Страница 11: ...11 6 Block Diagram 6 1 CS PS9JKT CU PS9JKT...
Страница 12: ...12 6 2 CS PS12JKT CU PS12JKT...
Страница 13: ...13 7 Wiring Connection Diagram 7 1 Indoor Unit...
Страница 14: ...14 7 2 Outdoor Unit 7 2 1 CU PS9JKT...
Страница 15: ...15 7 2 2 CU PS12JKT...
Страница 16: ...16 8 Electronic Circuit Diagram 8 1 Indoor Unit...
Страница 17: ...17 8 2 Outdoor Unit 8 2 1 CU PS9JKT...
Страница 18: ...18 8 2 2 CU PS12JKT...
Страница 21: ...21 9 2 Outdoor Unit 9 3 Main Printed Circuit Board 9 3 1 CU PS9JKT...
Страница 22: ...22...
Страница 23: ...23 9 3 2 CU PS12JKT...