14.4.22 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During cooling and heating operation, when an input over-current (16.8A) is detected by checking the input current
value being detected by current transformer (CT) with the compressor running.
Malfunction Caused
•
Over-current due to compressor failure.
•
Over-current due to defective outdoor unit PCB.
•
Over-current due to defective inverter main circuit electrolytic capacitor.
•
Over-current due to excessive refrigerant.
Troubleshooting
Turn off power supply. Check the main
circuit electrolytic capacitor.
When F98 indication happens
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Get restarted and measure the input
current.
NO
Is Input current > 16.8A?
•
Replace the outdoor unit PCB.
NO
YES
Normal?
Check refrigerant amount.
•
Repair the pipe flare or union nuts.
Reclaim and recharge refrigerant.
•
Reclaim and recharge with correct
amount of refrigerant.
Excess refrigerant?
YES
NO
YES
NO
•
Replace outdoor unit PCB
•
Replace outdoor unit compressor
Содержание CS-PS9JKT
Страница 7: ...7 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Страница 8: ...8 4 Dimensions 4 1 Indoor Unit...
Страница 10: ...10 5 Refrigeration Cycle Diagram...
Страница 11: ...11 6 Block Diagram 6 1 CS PS9JKT CU PS9JKT...
Страница 12: ...12 6 2 CS PS12JKT CU PS12JKT...
Страница 13: ...13 7 Wiring Connection Diagram 7 1 Indoor Unit...
Страница 14: ...14 7 2 Outdoor Unit 7 2 1 CU PS9JKT...
Страница 15: ...15 7 2 2 CU PS12JKT...
Страница 16: ...16 8 Electronic Circuit Diagram 8 1 Indoor Unit...
Страница 17: ...17 8 2 Outdoor Unit 8 2 1 CU PS9JKT...
Страница 18: ...18 8 2 2 CU PS12JKT...
Страница 21: ...21 9 2 Outdoor Unit 9 3 Main Printed Circuit Board 9 3 1 CU PS9JKT...
Страница 22: ...22...
Страница 23: ...23 9 3 2 CU PS12JKT...