8-18
Operations of each contact
-
The BUSY flag for the axis 1 and 2 (X18, X19) indicating the state that a motor is running turns on
when the position control started, and it turns off when the operation completed.
-
The operation done flag for the axis 1 and 2 (X20, X21) indicating the state that an operation completed
turns on when the position control completed, and it will be held until any operation among the position
control, JOG operation, home return and pulser operation starts.
Sample program
Precautions on programming
-
To start the interpolation control, turn on the positioning start contact of the axis with the smallest
number in the same group.
-
In case of the center point specification, the X-axis auxiliary point is the center point of X axis, and the
Y-axis auxiliary point is the center point of Y axis. In case of the pass point, each pass point is set as
the pass point of X axis and Y axis.
-
When the control method is increment, both the center point and pass point are the increment
coordinatefrom the start point.
-
When the start point and the operaton done point is the same, it performs one circular operation when
using the center point method. However, when using the pass point method, an error occurs.
-
In case of the pass point method, when the start point, pass point and operation done pont exsit in the
same straight line, an arc is not comprised, and an error occurs.
-
When setting the long axis speed, the composite speed is faster than the long axis speed.
-
If any value such as a movement amount, acceleration time, deceleration time or target speed is out of
the specified range, a setting value error will occur when the position control starts.
-
The number of the startup contact and flag varies depending on the number of axes and the installation
position.
-
The specified slot number varies depending on the installation position of the unit.
Содержание AFP243710
Страница 16: ...xiv ...
Страница 17: ...Chapter 1 Functions of Unit and Restrictions on Combination ...
Страница 21: ...Chapter 2 Parts and Functions ...
Страница 24: ...2 4 ...
Страница 25: ...Chapter 3 Wiring ...
Страница 39: ...Chapter 4 Power On Off and Items to Check ...
Страница 44: ...4 6 ...
Страница 45: ...Chapter 5 Preparation For Operation ...
Страница 53: ...5 9 ...
Страница 55: ...Chapter 6 I O Allocation ...
Страница 63: ...Chapter 7 Setting Tool Configurator PM ...
Страница 87: ...7 25 Setting Font Select Option Font in the menu bar The following dialog is shown ...
Страница 102: ...7 40 ...
Страница 103: ...Chapter 8 Automatic Operation Position Control ...
Страница 115: ...8 13 ...
Страница 116: ...8 14 When the X axis and Y axis is the moving axes each axis in the above diagram is replaced ...
Страница 129: ...8 27 Reference Chapter 10 Manual Operation Home Return ...
Страница 139: ...Chapter 9 Manual Operation JOG Operation ...
Страница 144: ...9 6 ...
Страница 145: ...Chapter 10 Manual Operation Home Return ...
Страница 151: ...Chapter 11 Manual Operation Pulser Operation ...
Страница 155: ...Chapter 12 Stop Functions ...
Страница 158: ...12 4 ...
Страница 159: ...Chapter 13 Supplementary Functions ...
Страница 171: ...Chapter 14 Precautions During Programming ...
Страница 175: ...Chapter 15 Errors and Warnings ...
Страница 186: ...15 12 ...
Страница 187: ...Chapter 16 Troubleshooting ...
Страница 190: ...16 4 ...
Страница 191: ...Chapter 17 Specifications ...
Страница 241: ...Chapter 18 Dimensions ...
Страница 242: ...18 2 18 1 FP2 Positioning Unit Interpolation Type 2 axis type Unit mm 4 axis type Unit mm ...
Страница 243: ...Chapter 19 Sample Programs ...
Страница 247: ...19 5 ...
Страница 250: ...19 8 ...
Страница 251: ...Chapter 20 Driver Wiring ...
Страница 261: ......