3 Powering Up the 5645
Microstep Indexer/Drive
In this Chapter
This chapter explains how to power up the 5645 after installation.
Topics are:
Testing the installation
Troubleshooting
Repairing or replacing the 5645
3.1 Testing the Installation
Background
Perform the following test procedure to verify that the 5645 is
installed properly, and that it was not damaged internally during
shipment.
Configuration
The installation test power-up procedure requires a motor and
computer or terminal to test the basic functionality of the 5645.
A computer or terminal is required for complete testing.
Procedure
First, connect the computer or terminal by referring to Chapter 1
in the Programming Manual, “Setting up for Programming” (use
the “Terminal Emulator” Mode for this test). Test your
installation as follows:
WARNING
Perform this initial power-up with the motor shaft disconnected
from the load. Improper wiring or undiscovered shipping
damage could result in undesired motor motion. Be prepared to
remove power if excessive motion occurs.
5645 Installation and Hardware Manual
3 - 1