Input or Output
Signal
Pin
Number
Explanation
Input 10 (Limit +, cw)
Input 11 (Limit -, c.cw)
J5-2
J5-3
These inputs limit rotation direction. To set:
Limit+ (clockwise),
program PREDEF.INP10 = 1
Limit - (counter-clockwise),
program PREDEF.INP11 = 1
Input 12 (Start)
J5-4
This input starts motor motion using the GO
statement, or starts the program using the
RUN command. Activate this input by
programming PREDEF. INP12 = 1. Change
the value of RMT.START for other options.
Input 13 (Stop)
J5-5
This input stops program execution. Any
motion in progress is stopped immediately.
Activate this input by programming
PREDEF.INP13 = 1.
Note: Do not use input 13 for an emergency
stop to prevent personal injury. Use a
hard-wired switch connected to the power
source for an emergency stop.
Input 14 (Jog+, cw)
Input 15 (Jog-, c.cw)
J5-6
J5-7
These inputs control rotation direction and
speed. This function is useful for testing
because it only requires an enable signal for
automatic motor running; a program is not
needed. To set:
Jog +,
program PREDEF.INP14 = 1
Jog -,
program PREDEF.INP15 = 1
Note: Jog inputs will not initiate jogging if a
program is running.
5645 Installation and Hardware Manual