D-160TS-7-E
32
■ Status output assignment
A function can be assigned to status output.
Select a function from: None (non), Error output (Er), Error/Alarm output (Er-AL), High-Low alarm
output (F.A), and Error/High-Low alarm output (Er-F.A)
■ Status output mode
Mode (logic) of status output can be set.
Select from normally open (normally FET OFF) and normally closed (normally FET ON).
Normally Open
(Normal condition)
(Alarm active)
(Back to normal condition)
Normally Closed
(Normal condition)
(Alarm active)
(Back to normal condition)
FET OFF
FET ON
FET OFF
FET ON
Fig. 14.1
14. STATUS OUTPUT
This flowmeter is capable of status output of error/alarm condition.
Status output related setting can be done at "Out Pt" sub-menu of setting menu.
Status output is of open drain output (equivalent of open collector).