Code
Description
Cause (Authorization Denied)
Possible Solution
C
Pump error, premature
Busy
D
Pump error – reset quant-
ity exceeded
One (1) unit of pulse(s) being
received by the pump controller
without sensing the pump is “on”
PCT – Handle or Current sense
PCM – Handle or Voltage sense
K800 Hybrid – Current sense
Verify pump controller is
set up for the correct sens-
ing method, verify pump
wiring is correct
E
No “pump handle busy”
Pump controller sensed pump on,
pulses were never received and the
first pulse timer was reached
Verify pulser is working;
verify pulser wiring
F
No fueling pulse
Pump controller sensed pump on,
pulses were never received and the
first pulse timer was reached.
Verify pusler is working
Verify pulser wiring
G
Pump currently active
Pump nozzle is engaged
Stop fueling and hang-up
the nozzle
I
Normal
Transaction terminated normally
J
Quantity limit exceeded
One of the quantity limits for the
transaction has been reached
Verify pump, card/ac-
count record quantity lim-
its are adequate and
adjust accordingly
K
Total transaction timeout
exceeded
Total transaction timeout exceeded
Verify total transaction
fueling time is adequate
for the pump and adjust
accordingly
L
Pulser error
Only on flow switch applications;
pulses not being received within five
(5) seconds after the flow switch
activation
Verify pulser is working,
verify pulser wiring, verify
flow switch is not bad
N
Missing pulse detected
Pump controller sensed pump on,
pulses
O (01)
Communication error
The transaction was terminated
because communication was lost
with the pump controller
Verify communication wir-
ing is properly installed,
verify site power con-
ditions
Doc. No.: M1900 Rev.: 8
Page 58 of 65