Chapter 8:
Power, Environmental & Digital I/O
176
Console Server & RIM Gateway User Manual
Select if the UPS will be
Connected Via
USB or over pre-configured serial port or via SNMP/HTTP/HTTPS over
the preconfigured network Host connection
When you select a network UPS connection then the corresponding Host Name/Description that you set up for
that connection will be entered as the
Name
and
Description
for the power device. Alternately if you selected to
Connect Via
a USB or serial connection then you will need to enter a
Name
and
Description
for the power
device (and these details will also be used to create a new Managed Device entry for the serial/USB connected
UPS devices)
Enter the login details. This
Username
and
Password
is used by
slaves
of this UPS (i.e. other computers that
are drawing power through this UPS) to connect to the
console server
to monitor the UPS status so they can shut
themselves down when battery power is low. Monitoring will typically be performed using the
upsmon
client
running on the slave server (refer
section 8.2.3
)
Note
: These login credentials are not related the
Users
and access privileges you will have configured in
Serial &
Networks: Users & Groups
Select the action to take when UPS battery power becomes critical i.e. Shut down the UPS (or Shut down all
Managed UPSes) or simply Run until failure
Note
: The shutdown script
/etc/scripts/ups-shutdown
can be customized so, in the event of a critical power failure (when
the UPS battery runs out) you can perform program the console server to perform "last gasp" actions using
before power is lost! Refer online FAQ for details. However it generally is much simpler to perform such "last
gasp" actions by triggering Auto Response on the UPS hitting
batt
or
lowbatt.
Refer Chapter 7
If you have multiple UPSes and require them to be shut down in a specific order, specify the
Shutdown Order
for this UPS. This is a whole positive number, or
-1
.
0s
are shut down first, then
1s
,
2s
, etc.
-1s
are not shut
down at all. Defaults to
0
Select the
Driver
that will be used to communicate with the UPS. Most
console servers
are preconfigured so the
drop down menu presents full selection of drivers from the latest Network UPS Tools (NUT version 2.4)
However for CM4001/8 and SD4001/2/8 models you will need to upload the driver you need from
Click
New Options
in
Driver Options
if you need to set driver-specific options for your selected NUT driver and
hardware combination (more details at http://www.networkupstools.org/doc)
Содержание ACM5000
Страница 3: ......
Страница 10: ...Table of Contents 10 Console Server RIM Gateway User Manual...
Страница 11: ......
Страница 94: ...Chapter 5 Firewall Failover and Out of Band 94 Console Server RIM Gateway User Manual...
Страница 119: ......
Страница 149: ......
Страница 191: ......
Страница 205: ......
Страница 225: ......
Страница 303: ......
Страница 313: ......
Страница 323: ......