Chapter 7:
Alerts and Logging
162
Console Server & RIM Gateway User Manual
Similarly you can specify the specific
Subject Line
that will be sent with the email. Generally the email subject will
contain a truncated version of the alert notification message (which is contained in full in the body of the email).
However some SMS gateway service providers require blank subjects or require specific authentication headers
to be included in the subject line
Click
Apply Settings
to activate SMS-SMTP connection.
SMS via Cellular Modem
To use an attached or internal cellular modem for SMS the
Administrator
must enable SMS:
Select
Cellular Modem
In the
SMS Settings
field
Check
Receive Messages
to enable incoming SMS messages to be received. A custom script will be called on
receipt of incoming SMS messages
You may need to enter the phone number of the carrier’s
SMS Message Centre
(only if advised by your carrier or Support)
Click
Apply Settings
to activate SMS-SMTP connection
Note
The option to directly send SMS alerts via the cellular modem was included in the Management GUI in V3.4.
Advanced
console servers
have had the gateway software (
SMS Server Tools 3)
embedded since V3.1 however
you this could only be accessed from the command line to send SMS messages (refer online FAQ).
7.5.3 Send SNMP Trap alerts
The
Administrator
can configure the Simple Network Management Protocol (SNMP) agent that resides on the
console
server
to send SNMP trap alerts to an NMS management application:
Select
Alerts & Logging: SNMP
Select
Primary SNMP Manager
tab. The Primary and Secondary SNMP Manager tabs are used to configure where
and how outgoing SNMP alerts and notifications are sent. If you require your
console server
to send alerts via SNMP
then, at a minimum, a Primary SNMP Manager must be configured. Optionally, a second SNMP Network Manager
with its own SNMP settings can be specified on the
Secondary SNMP Manager
tab
Note:
All console servers can also be configured to provide status information on demand using
snmpd
. This SNMP
agent is configured using the
SNMP Service Detail
on
Alerts & Logging: SNMP
- as described in Chapter 15
Содержание ACM5000
Страница 3: ......
Страница 10: ...Table of Contents 10 Console Server RIM Gateway User Manual...
Страница 11: ......
Страница 94: ...Chapter 5 Firewall Failover and Out of Band 94 Console Server RIM Gateway User Manual...
Страница 119: ......
Страница 149: ......
Страница 191: ......
Страница 205: ......
Страница 225: ......
Страница 303: ......
Страница 313: ......
Страница 323: ......