82 / 181
Manual-ZintoA_final_ger_engl_it_20081017.doc
05.11.2008, Dipl.-Ing. S. Spitzley
6.2.2.2 Rear view of Batterypack:
Figure 11: Rear view of ZINTO A 1500 Batterypack,
ZINTO A 2000 Batterypack
Figure 12: Rear view of ZINTO A 3000 Batterypack
The power backup time can be extended by operating several
batterypacks in parallel. You will find a complete list of the
possible variations as well as the power backup times that can
be achieved in the table below. It is strongly recommended not
to exceed the maximum number of batterypacks:
Power backup time (min.)
at 50% / 100% load
Model
Control
unit
+ 1 BP
+ 2 BP
+ 3 BP
+ 4 BP
ZINTO A 800
23 / 6
-
-
-
-
ZINTO A 1000
14 / 6
-
-
-
-
ZINTO A 1500
-
16 / 7
40 / 16
67 / 28
95 / 40
ZINTO A 2000
-
14 / 6
34 / 15
56 / 25
78 / 36
ZINTO A 3000
13 / 5
53 / 25
96 / 46
140 / 69
185 / 93
Table 4: Power backup time with additional Batterypacks
(BP = Batterypack)