113 / 181
Manual-ZintoA_final_ger_engl_it_20081017.doc
05.11.2008, Dipl.-Ing. S. Spitzley
Step 2:
After the selection and acceptance of the
output voltage, the
Input
menu command is
opened. By pressing again for one second
you can select between the operating modes
given. To accept a selection, press for 3
seconds.
Enter button for accepting the configuration.
LED indicator for the selected operating
mode. The operating modes differ in the vary-
ing tolerance thresholds.
Default =
Normal
.
Normal: Input
voltage
tolerance:
+/- 20%.
Generator: Input voltage tolerance as for
Normal, however lower limit
frequency reduced to 40Hz.
Input
Wide
Range:
Input voltage tolerance:
-30% /+20%.
Output
Indicator for the output voltage set,
default = 230V.
Line
Indicator for the
normal mode
. The LED indi-
cator is illuminated constantly if the input volt-
age is available and within tolerance.
Battery
Indicator for the
battery mode
. In the battery
mode the
Battery
LED flashes 1 x every 4
seconds. At low battery capacity the fre-
quency is increased to every 2 seconds.
Indication of the UPS utilisation.
76% - 100%
51% - 75%
26% - 50%
0% - 25%
Indication of the battery capacity.
76% - 100%
51% - 75%
26% - 50%
0% - 25%
Inverter
LED indicator for faulty inverter.
General
LED indicator for general fault, e.g. overload
or secondary short circuit.
Содержание ZINTO A 1000
Страница 1: ...www online ups com Manual ZINTO A Series A 800 A 1000 A 1500 A 2000 A 3000 ...
Страница 3: ...2 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...
Страница 63: ...62 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...
Страница 65: ...64 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...
Страница 123: ...122 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...