No. Problem
Cause
Solution
Mains wall socket
faulty.
Please contact electri-
cian.
Short circuit in the
UPS output or
overload.
3. Remove all loads
from the UPS.
Re-start UPS and
re-connect loads to
the UPS one after
the other.
4. Ensure the loads are
not faulty (internal
short circuit).
Internal fuse faulty.
Contact dealer.
Output fuse tripped
(ZINTO A 3000).
Check the output fuse.
2
UPS does not
provide any
output voltage.
UPS output detect-
ing overload or
short circuit.
Check the cable connec-
tion.
Ensure the output load
does not exceed the
max. rated load for the
UPS.
Battery not
charged.
Charge the battery as
per section 10.2.
3 Battery
power
too low.
Battery faulty due
to age.
Replace battery.
4
General
LED
UPS overload.
Shutdown all loads on
the UPS. Contact
dealer.
Table 10: Troubleshooting
If the table above does not solve your problem, please stop,
switch off the UPS and isolate it from the mains.
Please contact ONLINE hotline.
NOTE:
ONLINE hotline: +49 (0) 89 / 2 42 39 90 18
When calling the hotline it is imperative you have the following
information at hand:
•
Model
and
serial
number
•
Date of purchase and installation
•
Detailed description of the problem
The hotline provides free technical support and will decide on
the action to be taken based on the description of the problem.
Содержание ZINTO A 1000
Страница 1: ...www online ups com Manual ZINTO A Series A 800 A 1000 A 1500 A 2000 A 3000 ...
Страница 3: ...2 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...
Страница 63: ...62 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...
Страница 65: ...64 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...
Страница 123: ...122 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...