OnLine Power
6-44
LED SUM ALARM: UPS is failed by critical alarm condition.
6.21.4
Push " LOG" switch, then screen will show all events with date and name following screen is a sample.
Event log
Push "LOG" switch again, then screen will go to (1), and continuously keep rolling from (1), (2), and (3).
STATUS SCREEN SYSTEM MEASUREMENT SCREEN MULTI OUTPUTS
(1)
(2)
(3)
(1)
(2)
(3)
UPS NORMAL @ 3KVA
INPUT OK @ CHRG OFF
BATT OK @ DC OK
ON INVERT @ OUT OK
OUTPUT: 122V @ 01923W
INPUT:118V @ 19A
DCBUS: 166V @ NA A
BATT: 013V @+000A
OUTPUT VOLT: 122V
OUTPUT VOLT: 211V
OUTPUT VOLT: 244V
OUTPUT VOLT: 280V
2/24/08, 11 INP UV
2/24/08, 11 INP BAD
2/24/08, 11 INP BAD
2/24/08, 11 INP TEST
Push "FREEZE" switch, then previous screen before
freeze will show and display continuously without
rolling (see sample below)
OUTPUT: 122V @ 01923W
INPUT:118V @ 19A
DCBUS: 166V @ NA A
BATT: 113V @ +000A
If want to freeze (1) , (2) or (3) screen display, push "FREEZE"
switch at (2)for (1), at (3) for 2 and at (1) for 3 display
log
freeze
test
LOG
FREEZE
TEST