APPENDIX A - SPECIFICATIONS
Specifications for KVA, 0.8pf Units
POWER RATING (KVA/KW)
10/8 15/12 20/16 25/20 30/24 40/32 50/40
62.5/50
INPUT and OUTPUT
INPUT VOLTAGE (VAC)
Three Phase, 4-Wire plus Ground, 208Y/120 or 480Y/277 VAC (-20% to +15%)
OUTPUT VOLTAGE (VAC)
Three Phase, 4-Wire plus Ground, 208Y/120 or 480Y/277 VAC
OUTPUT FREQUENCY (Hz)
60 Hz +0.5 Hz
VOLTAGE REGULATION
+/-3%, Regulated within CBEMA curve
OUTPUT WAVE FORM
Sine-Wave <5% THD.
EFFICIENCY
Minimum 90%
CREST FACTOR
3 to 1 Typical
SURGE PROTECTION
The UPS will protect itself and the load against surges as defined in ANSI/IEEE C62.41 Categories A and B.
ISOLATION
Complete from line. Output neutral bonded to ground
NOISE ISOLATION
-120 dB Common-Mode; -60 kB Transverse-Mode
BATTERY
Sealed maintenance-free (AGM) battery
RECHARGE CURRENT
Conforms to UL Standards
EXTERNAL BATTERY
Provisions for hardwire connection of optional external battery cabinets or DC source.
BATTERY
BATTERY RUN TIME
Consult OnLine Power
BATTERY TYPE
Sealed, Maintenance-Free, AGM, VRLA type
NOMINAL BATTERY VOLTAGE
192 VDC
192 VDC
192 VDC
288 VDC
288 VDC
312 VDC
552 VDC
552 VDC
OVERCURRENT PROTECTION
Circuit Breaker
PACKAGING
Batteries not housed in Same Enclosure as electronic (See Table 2-2)