6.20 OPTIONAL ECM - EMERGENCY CONTROL MODULE – P/N 9100-1502
6.20.1 Installation
Indoor use only.
ECM is a universal mount unit.
Simple and fast installation in ceiling or wall mounted standard
single gang E-box, recommended box size 4”. Installation must be performed by a qualified electrician per
Installation, Operation and Maintenance Instructions provided with the EMC.
6.20.2 Operation
The emergency power is provided from a central lighting inverter that is automatically switched over to 24 hour
emergency power distribution panel. The room switch turns on and off both regular and emergency lights
simultaneously. This is accomplished by having the room switch leg power activate the Emergency Control Module.
Wire input#1 is connected internally to a sensing circuit. During a power interruption, this circuit causes contact X
to drop into a N.C. position. Please review wiring schematics.
6.20.3 Specification
Description: ECM - EMERGENCY CONTROL MODULE
Part Number: 9100-1502-01 - 120 VAC
9100-1502-02 - 277 VAC
Rating: Maximum Ballast load 1500 W, 120 and 277 VAC
20 A N.C. UL contact rating
High Voltage surge protectors
Approvals:
UL 924, NFPA 1104-2.4.1, OSHA
NEC 700 thru 700-26, 701-717,702-709, 705-750,
Operating Temperature: 210 to 150 F
Size:
2.75”W x 1.5”H x 1.25”D (overall)
Color:
Black
Weight:
8 oz.
ILLUSTRATION 6-13: ECM EMERGENCY CONTROL MODULE