OnLine Power
6-6
6.5
OPTIONAL TVSS P/N – 9100-1440-01
6.5.1 Operation
TVSS contains energy absorbing components designed for specific line configurations. The device has
two-stage protection. When protection components are damaged by absorbed transients, the device will
show a reserve flag indicating a need for replacement. At this time the device is still operational, due to
redundant circuits. After the second spike, the device will show and alarm condition indicating replacement
is mandatory. Remote indication contacts “TS” allows remote control of the protection status.
6.5.2 Specifications
Part Number
Description
9100-1440-01 TVSS
OPTION.
208V, 3PH, 40KVA 8/20US, THREE PHASE, REPLACEABLE
DIN RAIL, LED ALARM, AND INTERNAL DISCONNECTOR.
IEC61643-1 / EN61643-11
ANSI / IEEE C62.41 / UL1449, Second Edition –Feb.2007
CULUS / UL94-V2
3PHASE PLUS NEUTRAL
9100-1440-11
TVSS OPTION, 480V, 3PHASE, THREE PHASE, REPLACEABLE DIN RAIL,
LED ALARM, AND INTERNAL DISCONNECTOR.
IEC61643-1 / EN61643-11
ANSI / IEEE C62.41 / UL1449, Second Edition –Feb.2007
CULUS / UL94-V2
3PHASE PLUS NEUTRAL.
6.6
OPTIONAL NORMALLY ON/ NORMALLY OFF OUTPUT AUX. CIRCUIT BREAKERS – P/N
9100-1343-01 THRU -16
These circuit breakers are 1 pole, 20 A devices for protection of customer’s circuits.
Normally ON C.B. Option
Normally OFF C.B. Option
Normally OFF Delay C.B. Option
6.7
OPTIONAL EXTERNAL OUTPUT AUX. CIRCUIT BREAKERS IN PANEL BOARD – P/N 9100-
1439-01 THRU -03
6.7.1 Description
A matching external panel board with 1P 20A, (QO-Square D) circuit breakers is provided for power
distribution from the UPS output to critical loads. The panel board accommodates up to 42 breakers. A
main circuit breaker is provided with each panel board. See drawing 6001-03-15 for panel mounting
arrangement.
6.7.2 Specification
Part Number
Description
9100-1439-01
EXTERNAL OUTPUT AUX CBS OPTION IN A PANEL BOARD
1PH, CB. UP TO 24 (QO BREAKER) 125AMP.
9100-1439-02
EXTERNAL OUTPUT AUX CBS OPTION IN A PANEL BOARD
1PH, CB. UP TO 30 (QO BREAKER) 200AMP.
9100-1439-03
EXTERNAL OUTPUT AUX CBS OPTION IN A PANEL BOARD
1PH, CB. UP TO 42 (QO BREAKER) 225AMP.
2025-125
10KAIC @240V, 120/240V, APPLICATION
CB, 1PH, 20AMP QO BREAKER FOR 9100-1439-xx.