OnLine Power
A-3
UPS RATING
KVA/KW
INPUT
VOLT.
OUTPUT
VOLT.
INPUT
CURRENT
RECOM.
*OCPD
OUTPUT
CURRENT
RECOM.
*OCPD
BATT.
VOLT.
MAX.
BATT.
DISCH.
AMP
FULL
LOAD
BTU/HR
MAX.
TOTAL
UNIT
WEIGHT
FLOOR
LOADING
LBS/SQFT
3PHASE
3PHASE
NORM/MAX
NORM/MAX
UPS CAB
10KVA / 8KW
208Y/120
208Y/120
31/38
48
28/35
44
192
56
3032
1083
222
480Y/277
480Y/277
14/18
23
12/15
18
192
56
3032
1083
222
480Y/277
208Y/120
14/18
23
28/35
44
192
56
3032
1083
222
15KVA / 12KW
208Y/120
208Y/120
47/59
74
42/53
66
192
84
4549
1446
297
480Y/277
480Y/277
21/26
33
18/23
29
192
84
4549
1446
297
480Y/277
208Y/120
21/26
33
42/53
66
192
84
4549
1446
297
20KVA / 16KW
208Y/120
208Y/120
62/78
97
56/70
88
192
112
6066
1679
344
480Y/277
480Y/277
27/34
42
24/30
38
192
112
6066
1679
344
480Y/277
208Y/120
27/34
42
56/30
38
192
112
6066
1679
344
25KVA / 20KW
208Y/120
208Y/120
77/76
120
69/86
108
288
85
7582
1679
344
480Y/277
480Y/277
35/44
55
30/38
48
288
85
7582
1679
344
480Y/277
208Y/120
35/44
55
69/86
108
288
85
7582
1679
344
30KVA / 24KW
208Y/120
208Y/120
93/16
145
83/104
130
288
102
9098
1719
353
480Y/277
480Y/277
41/51
64
36/45
56
288
102
9098
1719
353
480Y/277
208Y/120
41/51
64
83/104
130
288
102
9098
1719
353
40KVA / 32KW
208Y/120
208Y/120
123/154
192
111/139
174
312
169
12131
2066
424
480Y/277
480Y/277
54/68
84
48/60
75
312
169
12131
2066
424
480Y/277
208Y/120
123/54
192
111/139
174
312
169
12131
2066
424
50KVA / 40KW
208Y/120
208Y/120
155/194
242
139/174
217
552
120
15164
2463
505
480Y/277
480Y/277
67/84
105
60/75
94
552
120
15164
2463
505
480Y/277
208Y/120
155/194
242
139/174
217
552
120
15164
2463
505
62.5KVA / 50KW
208Y/120
208Y/120
194/243
303
174/218
272
552
150
18000
2565
526
480Y/277
480Y/277
84/105
131
75/94
117
552
150
18000
2565
526
480Y/277
208Y/120
194/243
303
174/218
272
552
150
18000
2565
526
Recommended Input/Output Protective Device Ratings, BTU/Hr, and Floor Loading
Note:
Battery run time is very, consult factor for the battery Qty and cabinet arrangement for a certain battery run time.