6-47
6.21.6 (Continue)
Event Logger will log any event from the list below and attached a time stamp that include date and hour at the
event occurred (see sample screen below).
The local display on front of the Inverter will display the list of event logged when the LOG button is pressed for
approximately 2 seconds. The event logger to log up 50 events and display them 4 (four) at a time on the local
display.
Sample Screen
Event Logger
List of Events:
1) OUTPUT –
UNDER
VOLTAGE
OVER VOLTAGE
2) OUTPUT LOAD-
OVER LOAD
3) INPUT –
UNDER VOLTAGE
OVER VOLTAGE
INPUT BAD
4) BATTERY -
UNDER VOLTAGE
OVER VOLTAGE
CHARGER OFF
5) DC BUSS-
UNDER
VOLTAGE
OVER VOLTAGE
6) OVER TEMPERATURE
7) BATTERY TEST _
RECORDS AUTOMATIC TEST MONTHLY FOR 10 MINUTES
AND YEARLY FOR 90 MINUTES.
8) AUX. OUTPUT CIRCUIT BREAKER
AUX. C.B. TRIP
2/24/08, 11 INP UV
2/24/08, 11 INP BAD
2/24/08, 11 INP BAD
2/24/08, 11 INP TEST