OnLine Power
A-2
Specifications for KVA, 0.8pf Units (Continued)
MONITORING AND COMMUNICATIONS
INDICATORS
LCD Display Panel
RELAY INTERFACE
Dry Contacts for:
Sum Alarm (N.C.); Bypass On (N.O.); Loss of Input Power (N.O.); Low Battery (N.O.)
CONTACT RATING
125 Volts (AC or DC) Maximum; 1.25 Amperes Maximum; 30 Watts / 50 VA Maximum
INTERFACE CONNECTION
Hard Wired (Terminal Block)
ENVIRONMENTAL
SURGE WITHSTANDABILITY
ANSI C62.41-1980 Categories A & B
OPERATING TEMPERATURE
Meets NEMA Requirements
OPERATING RELATIVE HUMIDITY
0 to 95% Non-Condensing
ALTITUDE
Up to 6,000 Feet (1,829 Meters) with No De-Rating
COOLING
Air Cooled-Forced Fan
PHYSICAL (KVA/KW)
10/8 15/12 20/16 25/20 30/24 40/32 50/40
62.5/50
SIZE HxWxD in. (cm)
70 x 39 x 20 (177.8 x 99.1 x 50.8)
WEIGHT lbs (kg) with batteries
1655
1655
1998
2092
2186
2566
TBD
TBD
CONSTRUCTION
Painted Steel Enclosure with 3 Point Double Locking Front Door; and Full-length Door Hinge.
ENCLOSURE
Designed for Inside Installations
COLOR
Black
ACCESSIBILITY
Front - All Servicing is Through the Front; No Side or Rear Access is Required.
CABLE ENTRY
Top or sides
MOUNTING
Four (4) Holes Provided to Anchor Enclosure to Pedestal (Supplied by Others)