375
8-2-1 Standard Communications Parameters
The settings in DM 6645 and DM 6650 determine the main communications pa-
rameters, as shown in the following diagram.
The settings in bits 00 through 07 and bits 12 through 15 are valid only when pin
5 on the CPU’s DIP switch is OFF. Bits 08 though 11 are valid only in a PC set as
the master for a 1:1 link.
Communications mode
0: Host link
1: RS-232C
2: One-to-one link slave
3: One-to-one link master
4: NT link
15
0
Bit
DM 6645: RS-232C port
DM 6650: Peripheral port
Link words for one-to-one link
0: LR 00 to LR 63
1: LR 00 to LR 31
2: LR 00 to LR 16
Port settings
00: Standard communication parameters
01: According to setting in DM 6646 and DM 6651 (
(defaults: standard communications parameter and
Host Link mode)
The standard communications parameters are as shown in the following table.
Item
Setting
Start bits
1
Data length
7
Stop bits
2
Parity
Even
Baud rate
9,600 bps
Be sure to set the proper communications mode.
If the above parameters are acceptable, set the rightmost two digits (port set-
tings) to 00. To change the parameters, use the setting described next.
Parameters for Host Link and RS-232C Communications
Section 8-2
Содержание SYSMAC C200HS
Страница 1: ...Cat No W235 E1 05 C200HS SYSMAC Programmable Controllers...
Страница 2: ...C200HS Programmable Controllers Operation Manual Revised February 2002...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 379: ...371 SR word Corresponding key s Bit 279 03 04 05 3 06 07 VER 08 09 Monitoring Operation and Modifying Data Section 7 1...
Страница 470: ...468 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage...
Страница 471: ...469 Programmer Program Date Page TC address T or C Set value Notes TC address T or C Set value Notes Timers and Counters...