421
Parameters
Mode Data (Command)
“Mode data” consists of two digits (one byte) hexadecimal. With the leftmost two
bits, specify the PC operating mode. Set all of the remaining bits to “0”.
RUN mode
7
6
5
4
3
2
1
0
0
0
0
0
0
0
1
0
0
0
1
0
1
1
x 16
1
PROGRAM mode
MONITOR mode
Bit
Bit
Operation mode
This area is different
from that of STATUS
READ.
x 16
0
11-3-23 ERROR READ –– MF
Reads and clears errors in the PC. Also checks whether previous errors have
been cleared.
Command Format
@
M
F
x 10
0
x 10
1
x 10
1
x 10
0
:
↵
Node no.
Header
code
Terminator
FCS
Error clear
Response Format
@
M
F
x 10
0
x 10
1
x 16
1
x 16
0
x 16
3
x 16
2
x 16
1
x 16
0
x 16
3
x 16
2
x 16
1
x 16
0
↵
:
Node no.
Header
code
End code
Error information
(1st word)
Terminator
FCS
Error information
(2nd word)
Parameters
Error Clear (Command)
Specify 01 to clear errors and 00 to not clear errors (BCD). Fatal errors can be
cleared only when the PC is in PROGRAM mode.
Host Link Commands
Section 11-3
Содержание SYSMAC C200HS
Страница 1: ...Cat No W235 E1 05 C200HS SYSMAC Programmable Controllers...
Страница 2: ...C200HS Programmable Controllers Operation Manual Revised February 2002...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 379: ...371 SR word Corresponding key s Bit 279 03 04 05 3 06 07 VER 08 09 Monitoring Operation and Modifying Data Section 7 1...
Страница 470: ...468 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage...
Страница 471: ...469 Programmer Program Date Page TC address T or C Set value Notes TC address T or C Set value Notes Timers and Counters...