The following diagram shows the format for host link command (TXD) sent from
the C200HS. The C200HS automatically attaches the prefixes and suffixes,
such as the node number, header, and FCS.
@ X
X
X
X
X
X
.........
X
X
X
∗
CR
Header
code (EX)
Data (122 ASCII characters max.)
FCS
Node
number
Terminator
RS-232C Mode
N must be BCD from #0000 to #0256. The value of the control word determines
the port from which data will be output and the order in which data will be written
to memory.
Control Word
The value of the control word determines the port from which data will be read
and the order in which data will be written to memory.
Byte order
0: Most significant bytes first
1: Least significant bytes first
Not used. (Set to 00.)
Port
0: Specifies RS-232C port
(C200HS-CPU21-E/23-E/31-E/CPU33-E).
1: Specifies peripheral port.
Digit number:
3 2 1 0
The specified number of bytes will be read from S through S+(NP2)–1 and trans-
mitted through the specified port.
MSB LSB
S
1
2
S+1
3
4
S+2
5
6
S+3
7
8
When digit 0 of C is 0, the bytes of source data shown above will be transmitted in
this order: 12345678...
When digit 0 of C is 1, the bytes of source data shown above will be transmitted in
this order: 21436587...
Note When start and end codes are specified the total data length should be 256 bytes
max., including the start and end codes.
Flags
ER:
Another device is not connected to the peripheral port.
There is an error in the communications settings (PC Setup) or the oper-
and settings.
Indirectly addressed DM word is non-existent. (Content of *DM word is
not BCD, or the DM area boundary has been exceeded.)
The source words (S to S+(N
÷
2)–1) exceed the data area.
26405: RS-232C Port Communications Enabled Flag
26413: Peripheral Port Communications Enabled Flag
26705: Host Link Unit #0 Communications Enabled Flag
26713: Host Link Unit #1 Communications Enabled Flag
Serial Communications Instructions
Section 5-27
Содержание SYSMAC C200HS
Страница 1: ...Cat No W235 E1 05 C200HS SYSMAC Programmable Controllers...
Страница 2: ...C200HS Programmable Controllers Operation Manual Revised February 2002...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 379: ...371 SR word Corresponding key s Bit 279 03 04 05 3 06 07 VER 08 09 Monitoring Operation and Modifying Data Section 7 1...
Страница 470: ...468 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage...
Страница 471: ...469 Programmer Program Date Page TC address T or C Set value Notes TC address T or C Set value Notes Timers and Counters...