408
Response Format
@
R
L
x 10
1
x 10
0
x 16
1
x 16
0
:
↵
x 16
3
x 16
2
x 16
1
x 16
0
FCS
Node no.
Header
code
End code
Read data (1 word)
Read data (for number of words read)
Terminator
Parameters
Read Data (Response)
The contents of the number of words specified by the command are returned in
hexadecimal as a response. The words are returned in order, starting with the
specified beginning word.
11-3-3 HR AREA READ –– RH
Reads the contents of the specified number of HR words, starting from the speci-
fied word.
Command Format
@
R
H
FCS
x 10
1
x 10
0
x 10
3
x 10
2
:
↵
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
Node no.
Header
code
Beginning word
(0000 to 0099)
No. of words
(0001 to 0100)
Terminator
Response Format
@
R
H
x 10
1
x 10
0
x 16
1
x 16
0
:
↵
x 16
3
x 16
2
x 16
1
x 16
0
FCS
Read data (1 word)
Header
code
Node no.
End code
Terminator
Read data (for number of words read)
Parameters
Read Data (Response)
The contents of the number of words specified by the command are returned in
hexadecimal as a response. The words are returned in order, starting with the
specified beginning word.
11-3-4 PV READ –– RC
Reads the contents of the specified number of timer/counter PVs (present val-
ues), starting from the specified timer/counter.
Command Format
@
R
C
FCS
x 10
1
x 10
0
x 10
3
x 10
2
:
↵
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
No. of timers/counters
(0001 to 0512)
Beginning timer/counter
(0000 to 0511)
Header
code
Node no.
Terminator
Response Format
@
R
C
x 10
1
x 10
0
x 16
1
x 16
0
:
↵
x 10
3
x 10
2
x 10
1
x 10
0
FCS
Terminator
Read data (1 word)
Read data (for number of words read)
End code
Header
code
Node no.
Parameters
Read Data (Response)
The number of present values specified by the command is returned in hexade-
Host Link Commands
Section 11-3
Содержание SYSMAC C200HS
Страница 1: ...Cat No W235 E1 05 C200HS SYSMAC Programmable Controllers...
Страница 2: ...C200HS Programmable Controllers Operation Manual Revised February 2002...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 379: ...371 SR word Corresponding key s Bit 279 03 04 05 3 06 07 VER 08 09 Monitoring Operation and Modifying Data Section 7 1...
Страница 470: ...468 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage...
Страница 471: ...469 Programmer Program Date Page TC address T or C Set value Notes TC address T or C Set value Notes Timers and Counters...