67
Word(s)
Default
Function
Bit(s)
DM 6556
00 to 07
Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
1.2 K
08 to 15
Frame format
Start
Length
Stop
Parity
00:
1 bit
7 bits
1 bit
Even
01:
1 bit
7 bits
1 bit
Odd
02:
1 bit
7 bits
1 bit
None
03:
1 bit
7 bits
2 bit
Even
04:
1 bit
7 bits
2 bit
Odd
05:
1 bit
7 bits
2 bit
None
06:
1 bit
8 bits
1 bit
Even
07:
1 bit
8 bits
1 bit
Odd
08:
1 bit
8 bits
1 bit
None
09:
1 bit
8 bits
2 bit
Even
10:
1 bit
8 bits
2 bit
Odd
11:
1 bit
8 bits
2 bit
None
1 start bit, 7-bit
data, 1 stop bit,
even parity
DM 6557
00 to 15
Transmission delay
0000 to 9999: BCD in 10-ms units.
0 ms
DM 6558
00 to 07
Node number (Host Link)
00 to 31 (BCD)
0
08 to 11
Start code enable (RS-232C)
0: Disable; 1: Set
Disabled
12 to 15
End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
Disabled
DM 6559
00 to 07
Start code (RS-232C)
00 to FF (binary)
0000
08 to 15
12 to 15 of DM 6558 set to 0:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
12 to 15 of DM 6558 set to 1:
End code (RS-232C)
00 to FF (binary)
3-6-6 Special I/O Unit Area Settings
The setting in bits 08 through 15 of DM 6602 determines the size and location of
the Special I/O Unit Area, as shown in the following table.
Setting
Mode
Function
00
C200H-compatible
RAM Mode
DM 1000 through DM 2599 are used for the Special I/O Unit Area.
•
Data in the Special I/O Unit Area can be read/written.
•
The data cannot be converted to ROM.
01
C200H-compatible
ROM Mode 1
The contents of DM 7000 through DM 7999 are transferred to DM 1000 through DM 1999
at startup and DM 1000 through DM 1999 are used for the Special I/O Unit Area.
•
The UM Area Allocation operation must be performed beforehand.
•
The data is compatible with C200H applications that use EEPROM/EPROM.
•
ROM conversion is possible indirectly by converting DM 7000 through DM 7999 to ROM.
02
DM Linear Mode 1
DM 7000 through DM 7999 are used for the Special I/O Unit Area.
•
The UM Area Allocation operation must be performed beforehand.
•
DM 1000 through DM 1999 can be used as regular DM.
•
DM 7000 through DM 7999 can be converted to ROM.
DM (Data Memory) Area
Section 3-6
Содержание SYSMAC C200HE
Страница 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Страница 2: ......
Страница 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Страница 6: ...vi ...
Страница 10: ......
Страница 12: ......
Страница 380: ......
Страница 410: ......
Страница 438: ......
Страница 464: ......
Страница 474: ......
Страница 522: ......
Страница 538: ......
Страница 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 554: ......
Страница 560: ......
Страница 584: ......
Страница 585: ......
Страница 586: ...W303 E1 09 ...