62
Word(s)
Default
Function
Bit(s)
DM 6614
00 to 07
Servicing time for Communications Board port A
(effective when bits 08 to 15 are set to 01)
00 to 99 (BCD): Percentage of cycle time used to service port A.
Minimum: 0.26 ms; maximum 58.254 ms
No setting
(0000)
08 to 15
Communications Board port A servicing setting enable
00: Do not set service time (Fixed at 5%, 0.26 ms min.)
01: Use time in 00 to 07.
Service time is 10 ms when operation is stopped, regardless of this setting.
DM 6615
00 to 15
Reserved
---
DM 6616
00 to 07
Servicing time for RS-232C port (effective when bits 08 to 15 are set to 01)
00 to 99 (BCD): Percentage of cycle time used to service RS-232C port.
Minimum: 0.228 ms; maximum 58.254 ms
No setting
(0000)
08 to 15
(RS-232C port servicing setting enable)
00: Do not set service time (Fixed at 5%, 0.228 ms min.)
01: Use time in 00 to 07.
Service time is 10 ms when operation is stopped, regardless of this setting.
DM 6617
00 to 07
Servicing time for peripheral port (effective when bits 08 to 15 are set to 01)
00 to 99 (BCD): Percentage of cycle time used to service peripheral.
Minimum: 0.26 ms; maximum 58.254 ms
No setting
(0000)
08 to 15
Peripheral port servicing setting enable
00: Do not set service time (Fixed at 5%, 0.26 ms min.)
01: Use time in 00 to 07.
Service time is 10 ms when operation is stopped, regardless of this setting.
DM 6618
00 to 07
Cycle monitor time (effective when bits 08 to 15 are set to 01, 02, or 03)
00 to 99 (BCD)
×
setting unit (see 08 to 15)
00
08 to 15
Cycle monitor enable (Setting in 00 to 07
×
setting unit; 99 s max.)
00: 120 ms (setting in bits 00 to 07 disabled)
01: Setting unit: 10 ms
02: Setting unit: 100 ms
03: Setting unit: 1 s
00: 120 ms
DM 6619
00 to 15
Cycle time
0000: Variable (no minimum)
0001 to 9999 (BCD): Minimum time in ms
Variable
Interrupt/Refresh Processing (DM 6620 to DM 6623)
The following settings are accessed only once when program execution begins.
DM 6620
00 to 09
Special I/O Unit cyclic refresh (Bit number corresponds to unit number, PC
Link Units included)
0: Enable cyclic refresh and I/O REFRESH (IORF(97)) from main program
1: Disable (refresh only for I/O REFRESH from interrupt programs)
A setting of 01 (Disable) is valid only when the interrupt response is set to
high-speed response mode. It is not valid for normal interrupt response or for
Special I/O Units mounted in Slave Racks.
Enable
10 to 11
Reserved
---
12 to 15
Interrupt response
0:
Normal (C200H compatible)
Interrupts cannot be received when Host Link servicing, execution of a
single instruction, Remote I/O processing, or Special I/O processing is
being performed. The interrupt subroutine will be executed after the
processing is completed.
1:
High-speed Response (C200HS or C200HX/HG/HE)
Interrupts will be received when Host Link servicing, execution of a
single instruction, Remote I/O processing, or Special I/O processing is
being performed. If there is an interrupt input, the current processing will
be interrupted and the interrupt subroutine will be executed.
Normal
DM (Data Memory) Area
Section 3-6
Содержание SYSMAC C200HE
Страница 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Страница 2: ......
Страница 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Страница 6: ...vi ...
Страница 10: ......
Страница 12: ......
Страница 380: ......
Страница 410: ......
Страница 438: ......
Страница 464: ......
Страница 474: ......
Страница 522: ......
Страница 538: ......
Страница 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 554: ......
Страница 560: ......
Страница 584: ......
Страница 585: ......
Страница 586: ...W303 E1 09 ...