Group-2 High-density I/O Units and B7A Interface Units are allocated words be-
tween IR 030 and IR 049 according to I/O number settings made on them and do
not use the words allocated to the slots in which they are mounted. For 32-point
Units, each Unit is allocated two words; for 64-point Units, each Unit is allocated
four words. The words allocated for each I/O number are in the following tables.
Any words or parts of words not used for I/O can be used as work words or bits in
programming.
32-point Units
64-point Units
I/O number
Words
I/O number
Words
0
IR 30 to IR 31
0
IR 30 to IR 33
1
IR 32 to IR 33
1
IR 32 to IR 35
2
IR 34 to IR 35
2
IR 34 to IR 37
3
IR 36 to IR 37
3
IR 36 to IR 39
4
IR 38 to IR 39
4
IR 38 to IR 41
5
IR 40 to IR 41
5
IR 40 to IR 43
6
IR 42 to IR 43
6
IR 42 to IR 45
7
IR 44 to IR 45
7
IR 44 to IR 47
8
IR 46 to IR 47
8
IR 46 to IR 49
9
IR 48 to IR 49
9
Cannot be used.
A
IR 330 to IR 331
A
IR 330 to IR 333
B
IR 332 to IR 333
B
IR 332 to IR 335
C
IR 334 to IR 335
C
IR 334 to IR 337
D
IR 336 to IR 337
D
IR 336 to IR 339
E
IR 338 to IR 339
E
IR 338 to IR 341
F
IR 340 to IR 341
F
Cannot be used.
Note
Unit numbers A to F cannot be set when using the following CPU Units:
C200HE-CPU32(-Z), C200HE-CPU42(-Z), C200HG-CPU33(-Z), C200HG-
CPU43(-Z), C200HX-CPU34(-Z), and C200HX-CPU44(-Z). Set unit number 0
to 9 when using these CPU Units.
When setting I/O numbers on the High-density I/O Units and B7A Interface
Units, be sure that the settings will not cause the same words to be allocated to
more than one Unit. For example, if I/O number 0 is allocated to a 64-point Unit,
I/O number 1 cannot be used for any Unit in the system.
Group-2 High-density I/O Units and B7A Interface Units are not considered Spe-
cial I/O Units and do not affect the limit to the number of Special I/O Units allowed
in the System, regardless of the number used.
The words allocated to Group-2 High-density I/O Units correspond to the con-
nectors on the Units as shown in the following table.
Unit
Word
Connector/row
32-point Units
m
Row A
p
m + 1
Row B
64-point Units
m
CN1, row A
p
m + 1
CN1, row B
m + 2
CN2, row A
m + 3
CN2, row B
Note
1. Group-2 High-density I/O Units and B7A Interface Units cannot be mounted
to Slave Racks.
2. Refer to the
Installation Guide
for limitations on the number of Special I/O
Units that can be mounted to Slave Racks.
Allocation for Group-2
High-density I/O Units and
B7 Interface Units
See
note.
IR (Internal Relay) Area
Section 3-3
Содержание SYSMAC C200HE
Страница 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Страница 2: ......
Страница 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Страница 6: ...vi ...
Страница 10: ......
Страница 12: ......
Страница 380: ......
Страница 410: ......
Страница 438: ......
Страница 464: ......
Страница 474: ......
Страница 522: ......
Страница 538: ......
Страница 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 554: ......
Страница 560: ......
Страница 584: ......
Страница 585: ......
Страница 586: ...W303 E1 09 ...