26406:
SR 26406 will be turned ON when data has been received normally at
the peripheral port and will be reset when the data is read using
RXD(––) is executed.
265:
SR 265 contains the number of bytes received at the RS-232C port and
is reset to 0000 when RXD(––) is executed.
Note
Communications flags and counters can be cleared either by specifying 0000 for
N or using the Port Reset Bit (SR 25208 for peripheral port and SR 25209 for
RS-232C port).
5-27-2
TRANSMIT – TXD(––)
S:
First source word
IR, SR, AR, DM, HR, TC, LR
C
: Control word
IR, SR, AR, DM, HR, TC, LR, #
Ladder Symbols
Operand Data Areas
N:
Number of bytes
IR, SR, AR, DM, HR, TC, LR, #
TXD(––)
S
C
N
@TXD(––)
S
C
N
Limitations
S and S+(N
÷
2)–1 must be in the same data area.
N must be BCD from #0000 to #0256. (#0000 to #0061 in host link mode)
Description
When the execution condition is OFF, TXD(––) is not executed. When the
execution condition is ON, TXD(––) reads N bytes of data from words S to
S+(N
÷
2)–1, converts it to ASCII, and outputs the data from the specified port.
TXD(––) operates differently in host link mode and RS-232C mode, so these
modes are described separately.
Note
The following flags will be ON to indicate that communications are possible
through the various ports. Be sure the corresponding flag is ON before executing
TXD(––).
SR 26405:
RS-232C port
SR 26413:
Peripheral port
SR 26705:
Host Link Unit #0
SR 26713:
Host Link Unit #1
Host Link Mode
N must be BCD from #0000 to #0061 (i.e., up to 122 bytes of ASCII). The value of
the control word determines the port from which data will be output, as shown
below.
Byte order
0: Most significant bytes first
1: Least significant bytes first
CTS and DSR signal monitoring (see note)
0: Don’t monitor CTS and DSR signals.
1: Monitor the CTS signal. (Output to bit 15 of D.)
2: Monitor the DSR signal. (Output to bit 15 of D.)
3: Monitor the CTS and DSR signals. (Output to bits 15 and 14 of D.)
Auxiliary reception port (when DR-15 is 0.)
0: Internal RS-232C port
1: Communications port A
2: Communications port B
Port
0: RS-232C port
1: Peripheral port
2: Specifies Host Link Unit #0
3: Specifies Host Link Unit #1
Digit number:
3 2 1 0
Serial Communications Instructions
Section 5-27
Содержание SYSMAC C200HE
Страница 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Страница 2: ......
Страница 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Страница 6: ...vi ...
Страница 10: ......
Страница 12: ......
Страница 380: ......
Страница 410: ......
Страница 438: ......
Страница 464: ......
Страница 474: ......
Страница 522: ......
Страница 538: ......
Страница 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 554: ......
Страница 560: ......
Страница 584: ......
Страница 585: ......
Страница 586: ...W303 E1 09 ...