296
Execution of a step is completed either by execution of the next SNXT(09) or by
turning OFF the control bit for the step (see example 3 below). When the step is
completed, all of the IR and HR bits in the step are turned OFF. All timers in the
step except TTIM(––) are reset to their SVs. TTIM(––), counters, shift registers,
bits set or reset with SET or RSET, and bits used in KEEP(11) maintain status.
Two simple steps are shown below.
SNXT(09) LR 2000
STEP(08) LR 2000
00000
Step controlled by LR 2000
SNXT(09) LR 2001
STEP(08) LR 2001
00001
Step controlled by LR 2001
SNXT(09) LR 2002
STEP(08)
00002
Starts step execution
Ends step execution
1st step
2nd step
Address
Instruction
Operands
Address
Instruction
Operands
00000
LD
00000
00001
SNXT(09)
LR
2000
00002
STEP(08)
LR
2000
Step controlled by LR 2000
00100
LD
00001
00101
SNXT(09)
LR
2001
00102
STEP(08)
LR
2001
Step controlled by LR 2001
00200
LD
00002
00201
SNXT(09)
LR
2002
00202
STEP(08)
---
Steps can be programmed in consecutively. Each step must start with STEP(08)
and generally ends with SNXT(09) (see example 3, below, for an exception).
When steps are programmed in series, three types of execution are possible:
sequential, branching, or parallel. The execution conditions for, and the position-
ing of, SNXT(09) determine how the steps are executed. The three examples
given below demonstrate these three types of step execution.
Precautions
Interlocks, jumps, SBN(92), and END(01) cannot be used within step programs.
Bits used as control bits must not be used anywhere else in the program unless
they are being used to control the operation of the step (see example 3, below).
All control bits must be in the same word and must be consecutive.
If IR or LR bits are used for control bits, their status will be lost during any power
interruption. If it is necessary to maintain status to resume execution at the same
step, HR bits must be used.
Step Instructions
Section 5-24
Содержание SYSMAC C200HE
Страница 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Страница 2: ......
Страница 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Страница 6: ...vi ...
Страница 10: ......
Страница 12: ......
Страница 380: ......
Страница 410: ......
Страница 438: ......
Страница 464: ......
Страница 474: ......
Страница 522: ......
Страница 538: ......
Страница 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 554: ......
Страница 560: ......
Страница 584: ......
Страница 585: ......
Страница 586: ...W303 E1 09 ...