63
Word(s)
Default
Function
Bit(s)
DM 6621
00 to 07
Reserved
---
08 to 15
Special I/O Unit refresh (PC Link Units included)
00: Enable refresh for all Special I/O Units
01: Disable refresh for all Special I/O Units (but, not valid on Slave Racks)
A setting of 1 (Disable) is not valid for Special I/O Units mounted in Slave
Racks.
Enable
DM 6622
00 to 07
Scheduled interrupt time unit
00: 10 ms
01: 1 ms
10 ms
(0000)
08 to 15
Scheduled interrupt time unit enable
00: Disable (10 ms)
01: Enable setting in 00 to 07
DM 6623
00 to 15
Special I/O Unit cyclic refresh (PC Link Units included)
(Bit numbers 00 to 15 correspond to unit numbers 0 to F.)
0: Enable cyclic refresh and I/O REFRESH (IORF(97)) from main program
1: Disable (refresh only for I/O REFRESH from interrupt programs)
A setting of 01 (Disable) is valid only when the interrupt response is set to
high-speed response mode. It is not valid for normal interrupt response or for
Special I/O Units mounted in Slave Racks.
Enable
DM 6624 to
DM 6644
00 to 15
Reserved
---
RS-232C Port Settings (DM 6645 to DM 6649)
The following settings are accessed continually while the PC is ON.
DM 6645
00 to 03
Port settings
0: Standard (Host Link or peripheral bus serial communications mode, 1
start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps)
1: Settings in DM 6646
Standard
04 to 07
CTS control setting
0: Disable CTS control
1: Enable CTS control
Disable
08 to 11
Words linked for 1:1 PC Link
0: LR 00 to LR 63; 1: LR 00 to LR 31; 2: LR 00 to LR 15
Maximum PT node number for 1:N NT Link
1 to 7 BCD (1 to 3 with a C200HE-CPU
-E
PC)
LR 00 to LR 63
12 to 15
Serial communications mode
0: Host Link; 1: RS-232C; 2: 1:1 PC Link slave; 3: 1:1 PC Link master;
4: 1:1 NT Link; 5: 1:N NT Link
Host Link
DM 6646
00 to 07
Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
1.2 K
08 to 15
Frame format
Start
Length
Stop
Parity
00:
1 bit
7 bits
1 bit
Even
01:
1 bit
7 bits
1 bit
Odd
02:
1 bit
7 bits
1 bit
None
03:
1 bit
7 bits
2 bit
Even
04:
1 bit
7 bits
2 bit
Odd
05:
1 bit
7 bits
2 bit
None
06:
1 bit
8 bits
1 bit
Even
07:
1 bit
8 bits
1 bit
Odd
08:
1 bit
8 bits
1 bit
None
09:
1 bit
8 bits
2 bit
Even
10:
1 bit
8 bits
2 bit
Odd
11:
1 bit
8 bits
2 bit
None
1 start bit, 7-bit
data, 1 stop bit,
even parity
DM 6647
00 to 15
Transmission delay
0000 to 9999: BCD in 10-ms units.
0 ms
DM (Data Memory) Area
Section 3-6
Содержание SYSMAC C200HE
Страница 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Страница 2: ......
Страница 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Страница 6: ...vi ...
Страница 10: ......
Страница 12: ......
Страница 380: ......
Страница 410: ......
Страница 438: ......
Страница 464: ......
Страница 474: ......
Страница 522: ......
Страница 538: ......
Страница 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 554: ......
Страница 560: ......
Страница 584: ......
Страница 585: ......
Страница 586: ...W303 E1 09 ...