493
Limitations
Bits in SR 253 through SR 255 can’t be specified.
Only 15 timers/counters or 15 Transition Flags can be set/reset.
The UM settings are not checked when Transition Flags are specified, i.e., as
long as the Transition Flag address does not exceed 1023, the command will be
executed normally even if the specified Flag does not actually exist in the remote
PC.
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
---
OK
OK
OK
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
---
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect. (The forced set/reset/cancel data is 16 bytes long.)
Note
With Host Link Units, an error code of 14 (format error) won’t be returned if data
is specified for bit 15 for a timer/counter or Transition Flag. (The forced set/reset/
cancel data can be one byte long or 16 bytes long.)
An end code of 15 (entry number data error) will be returned if the operand, word
address, or bit parameter setting is incorrect. An end code of 15 will also be re-
turned if the a data specification of 0 or 1 is used for a timer or counter Comple-
tion Flag or for a Transition Flag.
An error code of 15 (entry number data error) will be returned if [$C, $D] is speci-
fied for the forced data when set to TC.
End code
Contents
00
Normal completion
01
Not executable in RUN mode
13
FCS error
14
Format error
15
Entry number data error
18
Frame length error
10-3-29 FORCED SET/RESET CANCEL –– KC
Cancels all forced set and forced reset bits (including those set by FORCED
SET, FORCED RESET, and MULTIPLE FORCED SET/RESET). If multiple bits
are set, the forced status will be cancelled for all of them.
Command Format
@
K
C
x 10
0
x 10
1
↵
Node no.
Header
code
Terminator
FCS
Response Format
@
K
C
x 10
0
x 10
1
x 16
1
x 16
0
↵
Node no.
Header
code
Terminator
FCS
End code
Host Link Commands
Section 10-3
Содержание SYSMAC C200HE
Страница 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Страница 2: ......
Страница 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Страница 6: ...vi ...
Страница 10: ......
Страница 12: ......
Страница 380: ......
Страница 410: ......
Страница 438: ......
Страница 464: ......
Страница 474: ......
Страница 522: ......
Страница 538: ......
Страница 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 554: ......
Страница 560: ......
Страница 584: ......
Страница 585: ......
Страница 586: ...W303 E1 09 ...