232
Flags
ER:
Mi and/or Su is not BCD.
Indirectly addressed DM word is non-existent. (Content of
DM word is
not BCD, or the DM area boundary has been exceeded.)
CY:
ON when the result is negative, i.e., when Mi is less than Su plus CY.
EQ
:
ON when the result is 0.
Caution
Be sure to clear the carry flag with CLC(41) before executing SUB(31) if its pre-
vious status is not required, and check the status of CY after doing a subtraction
with SUB(31). If CY is ON as a result of executing SUB(31) (i.e., if the result is
negative), the result is output as the 10’s complement of the true answer. To con-
vert the output result to the true value, subtract the value in R from 0.
Example
When 00002 is ON, the following ladder program clears CY, subtracts the con-
tents of DM 0100 and CY from the content of 010 and places the result in HR 20.
If CY is set by executing SUB(31), the result in HR 20 is subtracted from zero
(note that CLC(41) is again required to obtain an accurate result), the result is
placed back in HR 20, and HR 2100 is turned ON to indicate a negative result.
If CY is not set by executing SUB(31), the result is positive, the second subtrac-
tion is not performed, and HR 2100 is not turned ON. HR 2100 is programmed as
a self-maintaining bit so that a change in the status of CY will not turn it OFF
when the program is recycled.
In this example, differentiated forms of SUB(31) are used so that the subtraction
operation is performed only once each time 00002 is turned ON. When another
subtraction operation is to be performed, 00002 will need to be turned OFF for at
least one cycle (resetting HR 2100) and then turned back ON.
CLC(41)
@SUB(31)
010
DM 0100
HR 20
CLC(41)
@SUB(31)
#0000
HR 20
HR 20
TR 0
25504
HR 2100
00002
25504
HR 2100
First
subtraction
Second
subtraction
Turned ON to indicate
negative result.
00000
LD
00002
00001
OUT
TR
0
00002
CLC(41)
00003
@SUB(31)
010
DM
0100
HR
20
00004
AND
25504
00005
CLC(41)
00006
@SUB(31)
#
0000
HR
20
HR
20
00007
LD
TR
0
00008
AND
25504
00009
OR
HR
2100
00010
OUT
HR
2100
Address
Instruction
Operands
The first and second subtractions for this diagram are shown below using exam-
ple data for 010 and DM 0100.
BCD Calculations
Section 5-19
Содержание SYSMAC C200HE
Страница 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Страница 2: ......
Страница 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Страница 6: ...vi ...
Страница 10: ......
Страница 12: ......
Страница 380: ......
Страница 410: ......
Страница 438: ......
Страница 464: ......
Страница 474: ......
Страница 522: ......
Страница 538: ......
Страница 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 554: ......
Страница 560: ......
Страница 584: ......
Страница 585: ......
Страница 586: ...W303 E1 09 ...