xvii
6
EC Directives
6-1
Applicable Directives
•
EMC Directives
•
Low Voltage Directive
6-2
Concepts
EMC Directives
OMRON devices that comply with EC Directives also conform to the related
EMC standards so that they can be more easily built into other devices or the
overall machine. The actual products have been checked for conformity to EMC
standards (see the following note). Whether the products conform to the stan-
dards in the system used by the customer, however, must be checked by the
customer.
EMC-related performance of the OMRON devices that comply with EC Direc-
tives will vary depending on the configuration, wiring, and other conditions of the
equipment or control panel on which the OMRON devices are installed. The cus-
tomer must, therefore, perform the final check to confirm that devices and the
overall machine conform to EMC standards.
Note
Applicable EMC (Electromagnetic Compatibility) standards are as follows:
EMS (Electromagnetic Susceptibility):
EN61131-2
EMI (Electromagnetic Interference):
EN61000-6-4
(Radiated emission: 10-m regulations)
Low Voltage Directive
Always ensure that devices operating at voltages of 50 to 1,000 VAC and 75 to
1,500 VDC meet the required safety standards for the PC (EN61131-2).
6-3
Conformance to EC Directives
The C200HX/C200HG/C200HE PCs comply with EC Directives. To ensure that
the machine or device in which the C200HX/C200HG/C200HE PC is used com-
plies with EC directives, the PC must be installed as follows:
1, 2, 3...
1. The C200HX/C200HG/C200HE PC must be installed within a control panel.
2. Reinforced insulation or double insulation must be used for the DC power
supplies used for the communications and I/O power supplies.
3. C200HX/C200HG/C200HE PCs complying with EC Directives also con-
form to the Common Emission Standard (EN61000-6-4). Radiated emis-
sion characteristics (10-m regulations) may vary depending on the configu-
ration of the control panel used, other devices connected to the control pan-
el, wiring, and other conditions. You must therefore confirm that the overall
machine or equipment complies with EC Directives.
6-4
Relay Output Noise Reduction Methods
The C200HX/C200HG/C200HE PCs conform to the Common Emission Stan-
dards (EN61000-6-4) of the EMC Directives. However, the noise generated
when the PC is switched ON or OFF using the relay output may not satisfy these
standards. In such a case, a noise filter must be connected to the load side or
other appropriate countermeasures must be provided external to the PC.
Countermeasures taken to satisfy the standards vary depending on the devices
on the load side, wiring, configuration of machines, etc. Examples of counter-
measures for reducing the generated noise are given on page 137 in the
C200HX/C200HG/C200HE Programmable Controllers Installation Guide
(W302).
EC Directives
6
Содержание SYSMAC C200HE
Страница 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Страница 2: ......
Страница 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Страница 6: ...vi ...
Страница 10: ......
Страница 12: ......
Страница 380: ......
Страница 410: ......
Страница 438: ......
Страница 464: ......
Страница 474: ......
Страница 522: ......
Страница 538: ......
Страница 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 554: ......
Страница 560: ......
Страница 584: ......
Страница 585: ......
Страница 586: ...W303 E1 09 ...