1-18
Commands and Responses (CompoWay/F Communications)
Section 1-9
Co
m
p
o
W
a
y
/F
C
o
m
m
u
n
icat
io
ns
1-9-10 Write via Communications
Command
This command is used to enable or disable “Write via communications.” When
sent, it changes the set value of “Write via communications.”
When write via communications is disabled, communications cannot be used
to write setting data or send operation commands.
The initial setting is “disabled.”
This command can be used in both setting area 0 and setting area 1.
Response
Response codes: The above indicates a normal end. For the response codes,
see
1-7 Operation Commands (CompoWay/F Communications)
1-9-11 Reset
Command
This command resets the system to no-measurement status. It can only be
used in setting area 0.
Response
Response codes: The above indicates a normal end. For the response codes,
see
1-7 Operation Commands (CompoWay/F Communications)
1-9-12 Bank Selection
Command
This command can be used only when “Bank Selection” is set to “Key.”
This command is used to change between comparative set values preset in
banks. There are 8 banks numbered 0 to 7.
This command can be used in both setting area 0 and setting area 1.
Related information
Description
“00”
Write via communications disabled
“01”
Write via communications enabled
"30"
"05"
SRC
"00"
Command
code
Related
information
MRC
"30"
"05"
"0000"
Response code
SRC
MRC
Related information
Description
“00”
Reset
"30"
"05"
SRC
"01"
Command
code
Related
information
MRC
"30"
"05"
"0000"
Response code
SRC
MRC
Related information
Bank No. selected
“00” to “07”
0 to 7
"30"
"05"
SRC
"02"
Command
code
Related
information
MRC
Содержание K3HB
Страница 2: ...K3HB Digital Indicators Communications User s Manual Revised March 2005...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 21: ...Part 1 CompoWay F...
Страница 69: ...Part 2 DeviceNet...
Страница 95: ...6 10 Ladder Programming Examples Section 4 3 Remote I O Com munications...
Страница 103: ...7 8 Explicit Messages Specific to DeviceNet compatible Digital Indicators Section 5 3 Explicit Message Communications...
Страница 111: ...8 8 Message Communications Performance Section 6 2 Communications Performance...
Страница 127: ...Part 3 BCD Output...
Страница 147: ......