11-8
Programming Example 1: Connecting to a PLC
Section 1-5
BCD
C
o
m
m
uni
cat
ions
Note
(1) I/O allocations marked with an asterisk are not used in this programming
example.
(2) The pin numbers shown in the above table are the pin numbers of the D-
sub connector on the special BCD output cable (sold separately).
1-5-2
DM (Data Memory) Area
Read data is stored in the memory, as shown below.
1-5-3
Operation
In this programming example, IR 00113 in the CPU Unit of the PLC is turned
ON to read the measurement value of the Digital Indicator to the PLC and
store it in the DM area. No matter how long IR 00113 remains ON, data is
sampled only once.
1-5-4
Timing Chart
28*
MIN
Input
Minimum value output request
Output Unit, IR 0202*
29*
HOLD
Input
HOLD input
Output Unit, IR 0203*
30*
RESET
Input
RESET input
Output Unit, IR 0204*
31
POL
Output
Data polarity signal
Input Unit, IR 0107
Pin
number
Signal name
Signal
direction
Meaning
I/O allocation
IR 000
Polarity (bit 00)
10
4
digit (bits 00 to 03)
10
3
digit (bits 12 to 15)
10
2
digit (bits 08 to 11)
10
1
digit (bits 04 to 07)
10
0
digit (bits 00 to 03)
IR 000
IR 002
RUN
START
D (START)
Upward differentiation of START signal
KEEP
REQUEST
D.V.
D (D.V)
Upward differentiation of DATA VALID signal
Содержание K3HB
Страница 2: ...K3HB Digital Indicators Communications User s Manual Revised March 2005...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 21: ...Part 1 CompoWay F...
Страница 69: ...Part 2 DeviceNet...
Страница 95: ...6 10 Ladder Programming Examples Section 4 3 Remote I O Com munications...
Страница 103: ...7 8 Explicit Messages Specific to DeviceNet compatible Digital Indicators Section 5 3 Explicit Message Communications...
Страница 111: ...8 8 Message Communications Performance Section 6 2 Communications Performance...
Страница 127: ...Part 3 BCD Output...
Страница 147: ......