11-7
Precautions for BCD Programming
Section 1-4
B
CD
Com
m
uni
cat
ions
1-3-3
Operating Method
Setting with front keys is not required for models with a BCD output.
1-4
Precautions for BCD Programming
1,2,3...
1.
With models with a BCD output, only the measurement value, maximum
value, or minimum value can be read out.
2.
The "+" and "
−
" polarity correspond to low and high of the POL signal.
3.
Read data while the D.V. is ON.
4.
Data cannot be written from the PLC to the Digital Indicator.
1-5
Programming Example 1: Connecting to a PLC
The following programming example shows a single Digital Indicator con-
nected to the SYSMAC C500 (OMRON).
1-5-1
I/O Allocations
Pin
number
Signal name
Signal
direction
Meaning
I/O allocation
1
COM
GND: V0*
2
RD1-1
Output
1
Read data 10
0
digit
Input Unit, IR 0000
3
RD1-2
Output
2
Read data 10
0
digit
Input Unit, IR 0001
4
RD1-4
Output
4
Read data 10
0
digit
Input Unit, IR 0002
5
RD1-8
Output
8
Read data 10
0
digit
Input Unit, IR 0003
6
RD2-1
Output
1
Read data 10
1
digit
Input Unit, IR 0004
7
RD2-2
Output
2
Read data 10
1
digit
Input Unit, IR 0005
8
RD2-4
Output
4
Read data 10
1
digit
Input Unit, IR 0006
9
RD2-8
Output
8
Read data 10
1
digit
Input Unit, IR 0007
10*
RD3-1
Output
1
Read data 10
2
digit
Input Unit, IR 0008
11*
RD3-2
Output
2
Read data 10
2
digit
Input Unit, IR 0009
12*
RD3-4
Output
4
Read data 10
2
digit
Input Unit, IR 0010
13*
RD3-8
Output
8
Read data 10
2
digit
Input Unit, IR 0011
14*
RD4-1
Output
1
Read data 10
3
digit
Input Unit, IR 0012
15*
RD4-2
Output
2
Read data 10
3
digit
Input Unit, IR 0013
16*
RD4-4
Output
4
Read data 10
3
digit
Input Unit, IR 0014
17*
RD4-8
Output
8
Read data 10
3
digit
Input Unit, IR 0015
18*
RD5-1
Output
1
Read data 10
4
digit
Input Unit, IR 0100
19*
RD5-2
Output
2
Read data 10
4
digit
Input Unit, IR 0101
20*
RD5-4
Output
4
Read data 10
4
digit
Input Unit, IR 0102
21*
RD5-8
Output
8
Read data 10
4
digit
Input Unit, IR 0103
22*
OVER
Output
Data overflow, data underflow
Input Unit, IR 0104*
23*
D·V
Output
Data valid signal
Input Unit, IR 0105
24*
RUN
Output
RUN signal
Input Unit, IR 0106
25*
COM
GND: V0*
26*
REQ
Input
Measurement value output request
Output Unit, IR 0200
27*
MAX
Input
Maximum value output request
Output Unit, IR 0201*
Содержание K3HB
Страница 2: ...K3HB Digital Indicators Communications User s Manual Revised March 2005...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 21: ...Part 1 CompoWay F...
Страница 69: ...Part 2 DeviceNet...
Страница 95: ...6 10 Ladder Programming Examples Section 4 3 Remote I O Com munications...
Страница 103: ...7 8 Explicit Messages Specific to DeviceNet compatible Digital Indicators Section 5 3 Explicit Message Communications...
Страница 111: ...8 8 Message Communications Performance Section 6 2 Communications Performance...
Страница 127: ...Part 3 BCD Output...
Страница 147: ......