Indicators and Error Processing
The following table lists the indicator status when errors occur, the probable
causes and processing.
Indicator status
Probable cause
Remedy
MS: OFF
NS: OFF
The power is not being
supplied to the Digital
Indicator.
Supply communications power from
the DeviceNet connector.
The power voltage is
not within the permitted
range.
Use a power supply voltage within the
permitted range.
The Digital Indicator is
faulty.
Replace the Digital Indicator.
MS: Flashing red
NS: No change
A checksum error has
occurred in the parame-
ters registered in
EEPROM.
Repairs are required if this error per-
sists even if the parameters are reset.
Contact your nearest OMRON repre-
sentative.
A EEPROM hardware
error has occurred.
MS: ON red
NS: OFF
The Digital Indicator is
faulty.
Repairs are required. Contact your
nearest OMRON representative.
MS: ON green
NS: Flashing green
Waiting to connect to
DeviceNet communica-
tions.
Check the following items and restart
the Digital Indicator.
• Are lengths of cables (trunk and
branch lines) correct?
• Are cables short-circuited, broken,
or loose?
• Are cables wired correctly?
• Is terminating resistance connected
to both ends of the trunk line only?
• Is noise interference excessive?
• Is the power to the master ON?
The Digital Indicator is
faulty.
Repairs are required. Contact your
nearest OMRON representative.
MS: ON green
NS: ON red
The DeviceNet is in Bus
Off status.
Check the following items and restart
the Digital Indicator.
• Are lengths of cables (trunk and
branch lines) correct?
• Are cables short-circuited, broken,
or loose?
• Is terminating resistance connected
to both ends of the trunk line only?
• Is noise interference excessive?
Node addresses dupli-
cated.
Reset node addresses correctly.
The Digital Indicator is
faulty.
Repairs are required. Contact your
nearest OMRON representative.
MS: ON green
NS: Flashing red
A communications tim-
eout has occurred.
Check the following items and restart
the Digital Indicator.
• Are lengths of cables (trunk and
branch lines) correct?
• Are cables short-circuited, broken,
or loose?
• Is terminating resistance connected
to both ends of the trunk line only?
• Is noise interference excessive?
The Digital Indicator is
faulty.
Repairs are required. Contact your
nearest OMRON representative.
Содержание K3HB
Страница 2: ...K3HB Digital Indicators Communications User s Manual Revised March 2005...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 21: ...Part 1 CompoWay F...
Страница 69: ...Part 2 DeviceNet...
Страница 95: ...6 10 Ladder Programming Examples Section 4 3 Remote I O Com munications...
Страница 103: ...7 8 Explicit Messages Specific to DeviceNet compatible Digital Indicators Section 5 3 Explicit Message Communications...
Страница 111: ...8 8 Message Communications Performance Section 6 2 Communications Performance...
Страница 127: ...Part 3 BCD Output...
Страница 147: ......