7-3
Overview of Explicit Message Communications
Section 5-1
Expl
ic
it M
essage
C
o
m
m
uni
cat
ions
■
CompoWay/F Binary Commands
CompoWay/F binary commands are CompoWay/F communications com-
mands expressed in hexadecimal, and are easy to execute from ladder pro-
grams. CompoWay/F communications commands that include ASCII data,
however, cannot be sent or received. Therefore, Read Controller Attribute (05
03) and broadcasting (unit number = XX) cannot be used.
■
CompoWay/F ASCII Commands
CompoWay/F ASCII commands are CompoWay/F communications com-
mands expressed in ASCII, so numerical values must be converted to ASCII
when executing these commands from a ladder program. CompoWay/F
binary commands cannot be used. Broadcasting (unit number = XX) cannot
be used, but all other CompoWay/F communications commands can be sent
and received, including Read Controller Attribute (05 03), which cannot be
used with CompoWay/F binary commands.
Sending Explicit Messages Specific to DeviceNet-compatible Digital Indicators
The master can send explicit messages to a DeviceNet-compatible Digital
Indicator to control various operations supported only by DeviceNet-compati-
ble Digital Indicators and to read DeviceNet-specific settings and status infor-
mation.
These explicit messages are used to read and write maintenance information
specific to DeviceNet-compatible Digital Indicators.
5-1-3
Explicit Messages Basic Format
The basic formats of explicit message commands and responses are
described here.
Command Block
Destination Node Address
This parameter specifies the node address of the Controller to which the
explicit messages (commands) will be sent in single-byte (2-digit) hexadeci-
mal.
Service Code, Class ID, Instance ID, Attribute ID
These parameters specify the command type, processing target, and pro-
cessing details.
The Attribute ID does not need to be specified for some commands.
Data
Specifies the details of the commands, set values, etc. The data section is not
required for read commands.
Response Block
The following format is used when a normal response is returned for the sent
explicit message.
Destination
node
address
Service
code
Class ID
Instance ID
Attribute ID
Data
No. of bytes
received
Source node
address
Service code
Data
Содержание K3HB
Страница 2: ...K3HB Digital Indicators Communications User s Manual Revised March 2005...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 21: ...Part 1 CompoWay F...
Страница 69: ...Part 2 DeviceNet...
Страница 95: ...6 10 Ladder Programming Examples Section 4 3 Remote I O Com munications...
Страница 103: ...7 8 Explicit Messages Specific to DeviceNet compatible Digital Indicators Section 5 3 Explicit Message Communications...
Страница 111: ...8 8 Message Communications Performance Section 6 2 Communications Performance...
Страница 127: ...Part 3 BCD Output...
Страница 147: ......