114
Register Number Allocations in Detail
Chapter 7-7
Inverter Status 1 (Register 002C Hex)
Output Terminal Status (Register 002D Hex)
Communications Error (Register 003D Hex)
Bit No.
Function
0
During RUN (1: During RUN)
1
Zero speed (1: Zero speed)
2
Frequency agree (1: Frequency agree)
3
Warning (Nonfatal error) (1: Warning)
4
Frequency detection 1 (1: Output frequency
≤
n58)
5
Frequency detection 2 (1: Output frequency
≥
n58)
6
Inverter ready (1: Ready)
7
UV (1: UV)
8
Base block (1: Base block)
9
Frequency reference mode (1: Other than communications)
10
RUN command mode (1: Other than communications)
11
Overtorque detection (1: Overtorque detection)
12 Not
used.
13
Fault retry (1: Fault retry)
14 Fault
(1:
Fault)
15
Communications time-over: No normal communications for 2 s or more
(1: Communications time-over detecting)
Bit No.
Function
0
Multi-function contact output terminal MA (1: ON)
1 to 15
Not used.
Bit No.
Function
0
CRC error (1: Error)
1
Data length error (1: Error)
2 Not
used.
3
Parity error (1: Error)
4
Overrun error (1: Error)
5
Framing error (1: Error)
6
Communications time-over (1: Error)
7 to 15
Not used.
Содержание J7 series
Страница 12: ...XII...
Страница 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Страница 47: ...33 CHAPTER 3 Preparing for Operation and Monitoring 3 1 Nomenclature 34 3 2 Outline of Operation 35...
Страница 54: ...40 Outline of Operation Chapter 3 2...
Страница 102: ...88 Other Functions Chapter 6 7...
Страница 158: ...144 Option Specifications Chapter 9 3...
Страница 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Страница 172: ...158 List of Parameters Chapter 10...
Страница 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...