38
Outline of Operation
Chapter 3-2
Example of Forward/Reverse Selection Settings
Note
The direction of motor rotation can be changed, even during operation.
Example of Local/Remote Selection Settings
Note
1.
Local or remote selection is possible only when the Inverter is not in
operation. The present setting can be monitored when the Inverter is in
operation.
2.
Local or remote settings in multi-function input terminals can be changed
through the multifunction input terminals only.
3.
Any RUN command input will be ignored while the LO/RE indicator is lit. To
enable a RUN command, first turn the RUN command OFF and then press
the Mode Key to display an item that has a green indicator (FREF to
MNTR). Then input the RUN command again.
Key sequence
Indicator
Explanation
Display
example
Press the Mode Key repeatedly until the F/R indicator
is lit.
The present setting will be displayed.
For: Forward; rEv: Reverse
Use the Increment or Decrement Key to change the
direction of motor rotation. The direction of motor
rotation selected will be enabled when the display
changes after the key is pressed.
Key sequence
Indicator
Explanation
Display
example
Press the Mode Key repeatedly until the LO/RE
indicator is lit.
The present setting will be displayed.
rE: Remote; Lo: Local
Use the Increment or Decrement Key to set the
Inverter to local or remote mode. The selection will be
enabled when the display changes after the key is
pressed.
Содержание J7 series
Страница 12: ...XII...
Страница 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Страница 47: ...33 CHAPTER 3 Preparing for Operation and Monitoring 3 1 Nomenclature 34 3 2 Outline of Operation 35...
Страница 54: ...40 Outline of Operation Chapter 3 2...
Страница 102: ...88 Other Functions Chapter 6 7...
Страница 158: ...144 Option Specifications Chapter 9 3...
Страница 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Страница 172: ...158 List of Parameters Chapter 10...
Страница 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...