96
Inverter Settings
Chapter 7-2
7-2-2
Operation Command Selection (n02)
• Select the method to input the RUN or STOP command into the Inverter.
• This parameter is enabled in remote mode only. The Inverter in local
mode accepts the RUN command only through key sequences on the
Digital Operator.
Set Values
Note
1.
To input the RUN command through RS-422A/485 communications, set
this parameter to 2. Then the RUN command only through RS-422A/485
communications will be enabled.
2.
The RUN command can be input through RS-422A/485 with multi-function
input settings as well. For details, refer to
7-2-4 Setting the Multi-function
.
7-2-3
Frequency Reference Input Selection (n03)
• Select the method to input the frequency reference into the Inverter in
remote mode.
• Ten methods can be used to input the frequency reference in remote
mode. Select the ideal method according to the application.
Set Values
Note
1.
To input the frequency reference through RS-422A/485 communications,
set this parameter to 6. Then the frequency reference only through RS-
422A/485 communications will be enabled.
2.
The frequency reference can be input through RS-422A/485 with multi-
function input settings as well. For details, refer to
.
3.
The setting of n03 is valid for frequency reference 1, and is not related to
frequency references 2 to 8. Frequency references 2 to 8 are set in n22 to
n28.
n02
Operation Command Selection Register
0102 Hex
Changes during
operation
No
Setting
range
0 to 2
Unit of
setting
1
Default setting
0
Value Description
0
The RUN Key and STOP/RESET Key on the Digital Operator are enabled.
1
Multi-function input terminals are enabled in 2- or 3-wire sequence.
2
RS-422A/485 communications are enabled.
n03
Frequency Reference
Selection
Register
0103 Hex
Changes during
operation
No
Setting
range
0 to 4, 6
Unit of
setting
1
Default setting
0
Value Description
0
The FREQUENCY adjuster on the Digital Operator is enabled.
1
Frequency reference 1 (n21) is enabled.
2
Frequency reference control terminal for 0- to 10-V voltage input is enabled.
3
Frequency reference control terminal for 4- to 20-mA current input is enabled.
4
Frequency reference control terminal for 0- to 20-mA current input is enabled.
6
Frequency reference through communications is enabled.
Содержание J7 series
Страница 12: ...XII...
Страница 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Страница 47: ...33 CHAPTER 3 Preparing for Operation and Monitoring 3 1 Nomenclature 34 3 2 Outline of Operation 35...
Страница 54: ...40 Outline of Operation Chapter 3 2...
Страница 102: ...88 Other Functions Chapter 6 7...
Страница 158: ...144 Option Specifications Chapter 9 3...
Страница 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Страница 172: ...158 List of Parameters Chapter 10...
Страница 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...